Mr. Bernard P. Orlan January 30,2002 ■Indoor Air Quality Measurements Page 3 Stuyvesant High School (M477) ATC Project No. 15-19125-0246

Real-Time Environmental Measurements

ATC collected one hundred and five (105) sets of real-time environmental measurements consisting of one hundred and three (103) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:15 A.M. and concluded after 1:15 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 69.6°F to 74.8°F. All of the measurements were within the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 58.4 to 65.7 °F.

Relative Humidity

The relative humidity indoors ranged from 39.5 percent to 44.2 percent. All of the measurements were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 40.4 and 41.3 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 516 ppm to 1167 ppm. None of the CO2 measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 449 and 469 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1169 ppm (background level + 700 ppm). The highest reading, 1167 ppm, was in Room 840. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations was 0 - Ippm.

Respirable Particulates (PM2_5)

Respirable particulate concentrations* indoors ranged between 15 pg/m^ to 38 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 54 and 62 pg/m3.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, gth and 7th floors (See Attachment 1). The PM2,5 concentration range for those rooms

CITY_21MC100_003045186

NYC-WTC_000311432

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311432Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000311402

ATC memo detailing IAQ measurements at Stuyvesant High School for Feb 2002.

Similar indexed content

NYC-WTC_000255923

February 2002 IAQ report for Stuyvesant High School.

Similar indexed content

Compare copies and versions →