NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 6 pages

IAQ memo, Stuyvesant High School, Jan 2002

Machine-extracted title · confidence 53%

ATC report of IAQ measurements collected January 29, 2002 at Stuyvesant HS.

NYC-WTC_000311430–000311435
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan January 30,2002 Indoor Air Quality Measurements Page 2 Stuyvesant High School (M477) ATCProiectNo. 15-19125-0246

The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.

EVALUATION CRITERIA

Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 65-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.

TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

■ Si iW I * ______ Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^ ) 24-hour average Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = Amencan Industrial Hygiene Association

CITY_21MC100_003045185

NYC-WTC_000311431

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311431Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000311402

ATC memo detailing IAQ measurements at Stuyvesant High School for Feb 2002.

Similar indexed content

NYC-WTC_000255923

February 2002 IAQ report for Stuyvesant High School.

Similar indexed content

Compare copies and versions →