Mr. Bernard P. Orlan January 22, 2002 Indoor Air Quality Measurements Page 3 Stuvvesant High School (M477') ATC Proiect No. 15-19125-0246

Real-Time Environmental Measurements

ATC collected one hundred (100) sets of real-time environmental measurements consisting of ninety-six (96) in the school building and four (4) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 8:30 A.M. and concluded after 3:00 P.M.

Temperature

Indoor dry bulb temperature measurements ranged fi-om 68.3°F to 72.8°F. None of the measurements were above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAF Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 46.1 to 47.1 °F.

Relative Humidity

The relative humidity indoors ranged from 20.2 percent to 27.7 percent. All measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity levels were 25.6, 25.7, 26.4 and 26.5 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 425 ppm to 679 ppm. None of the CO2 measurements were above the ASHRAF Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentrations were 439, 440, 440 and 438 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1140 ppm (background level -h 700 ppm). The highest reading, 679 ppm, was in Cafeteria. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm.

Respirable Particulates (PM2.S)

Respirable particulate concentrations* indoors ranged between 10 pg/m^ to 26 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The outdoor respirable particulate concentrations were 27 and 34 pg/m^.

Filters with a higher efficiency rating were installed on the HVAC units that serve rooms on the 3rd, 4th, Qth and 7^^ floors (See Attachment 1). The PM2.5 concentration range for those rooms

ClTy_21MC100_003045010

NYC-WTC_000311335

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000311335Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000311421

ATC memo reporting indoor air quality measurements at Stuyvesant High School.

Similar indexed content

NYC-WTC_000255939

February 2002 IAQ measurements at Stuyvesant High School.

Similar indexed content

NYC-WTC_000311449

ATC memo documenting IAQ measurements collected Jan 31, 2002 at Stuyvesant HS.

Similar indexed content

NYC-WTC_000213118

Cover letter and report from ATC Associates detailing indoor air quality measurements collected at Stuyvesant High School on June 14, 2002.

Similar indexed content

NYC-WTC_000373210

ATC indoor air quality measurements report for Stuyvesant High School, June 17, 2002.

Similar indexed content

Compare copies and versions →