TEM analysis, Stuyvesant HS floors 1-10, Oct 2001

Machine-extracted title · confidence 55%

TEM analysis results for Stuyvesant HS floors 1-10,October 5, 2001.

NYC-WTC_000302856
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

ATC Environmental, Inc. 104 East 25th Street New York, New York 10010

N.Y.C. Board of Education Approved N.Y. State ELAP #10879 28-11 Queens Plaza North ACCREDITED NVLAP Lab Code # 1187 Long Island City, NY 11101 Report Date: 10/05/01

ASBESTOS FIBER ANALYSIS BY TRTiNSMISSION ELECTRON MICROSCOPY (TEM) With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS' Method; AHERA Final Rule, EPA Federal Register (40 CFR, Part 763), Vol. S2, No. 210, October 30, 1987

Sample Identi-icacion Analysis Parameters

Proj ecs/Site : Stuwesant H 3£^j;harnbers3t NY^J^ TEM Sample No.: 560S 60OL7 Floors 1-10 Date Received: 10/05/01 Grid Openings Analyzed:__ 4

Project Sample No.: SHS- 1>.'.O-10/5-10 Average Grid Oneninq: 1Q6.Q0 urn

Air Volume: 1353 liters Total Area Analyzed:0 jMAn rnm2

FiiCer Type: MCE 25 mm.clam., Pore Size: 0,45 um Analytical Sensitivity.■22 r s/2mi2 Effective Are?;; 3 85 mrn2 0.0046 s/cc

FIB ROUS PARTICULATESAWALYZED Number Observed CONCENTRATION Total Single Matrix Total. Struct. F2,lter Air Fibers: Bundles Clusters Struct Struct >=5um Struct/mrr.2 Struct/cc nam/ml

Chrysotile Asbestos 0 0 0 0 0 0 0.0 0.0000 0

Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0

Ambiguous 0 0 0 0 0 0 0,0 0.0000 0

Total asbtistos (includes ambiguous structures) 0 0 0.0 0 . 0000 0 Non-Asbestos 0 0 0 0 0 0 0.0 0.0000 N/A No Identification 0 0 0 0 0 0 0.0 0 . OOOO N/A

Totals (a:.1 Structures) 0 0 0.0 0 . 0000 N/A The estimated uncertainty cf this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED): None detected Amphibole Asbestos Type: None decected

The Analysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the quality specified for the method.

Analyzed by: Report Reviewed by:

Roman Peysakhov Michael A. Gorycki, Ph.D. Director of Electron Microscopy

CITY_21MC1OO_OO311267O

NYC-WTC_000302856

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000302856Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000270586

TEM asbestos analysis by SAED/EDS for air samples at New Stuyvesant High School.

Similar indexed content

Compare copies and versions →