* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.
TVOC Concentrations
TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC
concentration was also 0.0 ppm.
OBSERVATIONS
During this assessment, ATC noted the following:
• There was construction work going on in the plaza;
• The school building was occupied at the time of the assessment;
• No smoke odor was detected in the building
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of CO and TVOGs were within applicable standards and guidelines;
2. None of the PM2.5 measurements were above the NPAAQS of 65 pg/m^ or above the
USEPA recommended PM2.5 concentration of 40 pg/m^ for sensitive individuals and
children.
3. Eleven (11) of the temperature measurements were above the range of 68 to 75° F (at 50
percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating
season (wintertime conditions).
4. All of the indoor measurements of relative humidity were below the ASHRAE recommended
range of 30 to 60 percent for occupant comfort.
5. One (1) CO2 measurement was above the range recommended by ASHRAE 62-1999. All
others were below the maximum concentration.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 or 212.
Sincerely, Reviewedby:
TC ASSOCL4 TES INC.