Mr. Bernard P. Orlan February 15, 2002
Indoor Air Quality Assessment Page 3
P. S. 150M ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty-three
(33) from inside the school building and seven (7) from outdoors. All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 12:00 P.M. and concluded at
approximately 1:30 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.0°F to 76.8°F. Eleven (11) of the
measurements were above the range of 68 to 75 °F (at 50 percent relative humidity) as
recommended by the ASHRAE Staiidard 55-1992 during the heating season (wintertime
conditions). The outdoor temperature measurements ranged from 36.5 to 37.5°F.
Jielative Humidity
The relative humidity indoors ranged from 12.9 to 22.2 percent. All of the measurements were
below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements ranged from 11.9 to 12.5 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 613 ppm to 1302 ppm. One (1) of the CO2
measurements was above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
GO2 concentration was 509 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1209 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is occupant respiration.
The school building was occupied during ATC’s assessment.
QirbpnJi^oxideCpncentration
Carbon monoxide concentrations indoors were 0 ppms for the interior readings. These
concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO
concentration was 1 ppm for all collected readings.
Respirable Particulates (PM2^§)
Respirable particulate concentrations* indoors ranged between 10 pg/m^ to 27 pg/m^. None of
the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2 5
concentration for the entire school building was approximately 17 pg/m^. The PM2.5 average
concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive
individuals / children. The outdoor respirable particulate concentration measurements ranged
from 24 to 30 pg/m^ with an average of 27 pg/m^.