Mr. Bernard P. Orlan February 11, 2002
Indoor Air Quality Assessment Page 3
P. S. 150M ATC Project No. 15-19125-0289
Real-Time environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30)
from inside the school building and ten (10) from outdoors. All three floors of the school
building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 11:00 A.M. and concluded at
approximately 3:45 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 75.9°F to 82.2°F. All of the
measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as
recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime
conditions). The outdoor temperature measurements ranged from 53.6 to 55.5°F.
Relative Humidity
The relative humidity indoors ranged from 14.0 to 24.9 percent. All of the measurements were
below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor
relative humidity measurements ranged from 15.0 to 16.6 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 617 ppm to 1350 ppm. Two (2) of the CO2
measurements were above the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The maximum outdoor (background)
CO2 concentration was 483 ppm. Therefore, the maximum acceptable level of CO2 at this
location was 1183 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outside makeup air. The primary source of CO2 indoors is. occupant respiration.
Ilie school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppms for the interior readings. These
concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO
concentration was also 0 ppm for all collected readings.
Respirable Particulates (PM2,s)
Respirable particulate concentrations* indoors ranged between 13 pg/m^ to 34 pg/m^. None of
the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5
concentration for the entire school building was approximately 21 pg/m^. The PM2.5 average
concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive
individuals / children. The outdoor respirable particulate concentration measurements ranged
from 18 to 40 pg/m^ with an average of 28 pg/m^.