Mr. Bernard P. Orlan April 17, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M8941 ATC Project No. 15-19125-0290 Real-Time Environmental Measurements
ATC collected one hundred and eight (108) sets of real-time environmental measurements consisting of one hundred and two (102) in the school building and six (6) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings began at 10:30 A.M. and concluded after 5:00 P.M. The results are described below.
Temverature
Indoor dry bulb temperature measurements ranged from SO °F to 83.4 °F. All of the indoor measurements for temperature were above the range of 68 to 75 °F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature range was 78.4 °F to 80.2 °F.
Relative Humidity
The relative humidity indoors ranged from 41.9 percent to 55.6 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 48.8 to 51 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 612 ppm to 1048 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 603 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1303 ppm (background level -1- 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 2 ppm to 4 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations are 2 ppm to 4 ppm.
Respirable Particulates (PM2j)
Respirable particulate concentrations* indoors ranged between 20 pg/m^ to 35 pg/m^ with an average 24 ug/m^- All of the indoor and outdoor measurements for PM2.5 were below the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 32 pg/m^ to 38 pg/m^ with an average of 34 pg/m^.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.
CITY_21MC1OO_OO3O86638
NYC-WTC_000296783
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000410943
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394768
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410947
Follow-up IAQ report for the referenced NYC BOE project, June 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000380933
Indoor air quality measurements at H.S. for Leadership & [name] as part of BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292020
ATC IAQ measurements collected June 24, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410951
BOE-requested IAQ measurements at H.S. Leadership, June 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000335293
Indoor air quality measurements at M894; June 21, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296785
ATC IAQ measurements at 90 Trinity Place; report dated Apr 17, 2002; project 15-19125-0290.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292012
ATC IAQ measurements collected June 20-21, 2002 for the referenced BOE school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394787
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000296762
ATC IAQ measurements report for HS for Leadership & [name], Apr 15, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394783
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000260108
ATC IAQ measurements collected April 16, 2002 at the referenced school under BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394768
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394734
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000394783
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410943
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000211859
Letter and report from ATC Associates detailing indoor air quality measurements collected at the school on March 25, 2002, to evaluate possible contamination.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
IAQ memo regarding measurements at 90 Trinity Place for BOE, June 2002.
Similar indexed content
Indoor air quality measurements report for High School for Leadership & [name], Apr 2002.
Similar indexed content
Follow-up IAQ report for the referenced NYC BOE project, June 2002.
Similar indexed content
NYC-WTC_000380933
Indoor air quality measurements at H.S. for Leadership & [name] as part of BOE program.
Similar indexed content
ATC IAQ measurements collected June 24, 2002 for the referenced school.
Similar indexed content