Memo/letter: Indoor air quality, school IAQ

Machine-extracted title · confidence 52%

ATC report of IAQ measurements at a NYC school for BOE.

NYC-WTC_000295768–000295771
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr Bernard P Orlan March? 2002 Indoor Air Quality Assessment Page 4 H S for Leadershin & Public Service fM894') ATCProiectNo 15 19125 0290

TVOC Concentration

The TVOCs concentrations were 0 ppm inside the building These concentrations were below the AIHA guideline for odor control of 1 ppm The outdoor TVOC concentration was also 0 ppm

OBSERVATIONS

During this assessment ATC noted the following • The interior of the building appeared clean and free of dust and debris • The building was occupied at the time of the assessment • No smoke odor was detected m the building

FINDINGS

Based on the real time measurements the following findings are presented

1 Concentrations of respirable particles CO and TVOCs were below applicable standards and guidelines 2 One hundred and twenty (120) indoor measurements for relative humidity were below the ASHRAE recommended range of 30 to 60 percent for occupant comfort Eight (8) indoor measurements were within the ASHRAE recommended range 3 Six (6) indoor measurements for temperature were below and one (1) above the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55 1992 during the heating season (wintertime conditions) 4 Two (2) of the indoor measurements for CO2 were above the ASHRAE Standard 62 1999 recommended maximum concentration of <700 ppm above the background level The highest reading (1423 ppm) was measured in room 206 at 12 45 AM with 96 occupants

It IS our pleasure to provide these indoor air quality services to the New York City Board of Education If you have any questions about this report please call (212) 353 8280 extension 336 or 212

Sincerely Reviewed by J TC ASSOCIA TES INC

Svnel Javifl James R Cohn CIH CSP Senior Pr^ct Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC1OO_OO3O85336

NYC-WTC_000295771

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000295771Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →