Indoor air quality report, PS 234M, Mar 2002

Machine-extracted title · confidence 41%

IAQ measurements collected March 9–11, 2002 for PS 234M at Greenwich st school.

NYC-WTC_000294397–000294400
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan March 11,2002 Indoor Air Quality Assessment Page 3 F. S. 234M______________________________ ATC Project No. 15-19125-0279 Real-Time Environmental Measurements

ATC collected sixty (60) sets of real-time environmental measurements consisting of fifty (50) from inside the school building and ten (10) outdoors. All three floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 12:00 P.M, and concluded after 1:55 P.M.

Temperature

Indoor dry bulb temperature measurements ranged from 67.5 °F to 78.4 °F. One (1) indoor measurements was below and seven (7) indoor measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 44.8 to 70.8 °F.

Relative Humidity

The relative humidity indoors ranged from 29.7 percent to 44.4 percent. Forty-nine (49) of the measurements were within the ASlIRAE-rccommcnded range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 32 to 46.8 percent.

Carbon Dioxide Concentration

Carbon dioxjde concentrations indoors ranged from 820 ppm to 2780 ppm. Thirty-three (33) of the measurements were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CC)2 concentration was 799 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1499 ppm (background level + 700 ppm). The highest measurement was taken in room 229 at 1:10 PM. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 0 ppm.

Respirable Particulates (PM2 §)

Respirable particulate concentrations* indoors ranged between 27 pg/m^ to 109 pg/m^. Fifteen (15) indoor measurements were above the NPAAQS of 65 pg/m^ ■ Forty-five (45) of the fifty (50) instantaneous indoor measurements were above the EPA recommended guideline of 40pg/m3 for children and sensitive individuals. The average PM7.5 concentration for the entire school building was approximately 64 pg/m^. The outdoor respirable particulate concentration ranged from 80 to 139 pg/m3 with an average of 130 pg/m3. All of the outdoor instantaneous

CITY_21MC100_003083621

NYC-WTC_000294399

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000294399Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Page similarity is temporarily unavailable or this page has no indexed vector.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →