NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 1 page

Asbestos TEM analysis, New Stuyvesant HS, Oct 2001

Machine-extracted title · confidence 47%

TEM analysis; exterior/interior; New Stuyvesant HS; 10/26/01.

NYC-WTC_000293974
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

ATC Environmental, Inc. 104 East 25th Street New York, New York 10010

N.Y.C. Board of Education Approved N.Y. State ELAP #10879 28-11 Queens Plaza North ACCREDITED NVLAP Lab Code # 1187 Long Island City, NY 11101 Report Date: 10/27/01

ASBESTOS FIBER ANALYSIS BY TRTINSMISSION ELECTRON MICROSCOPY (TEM) With Fiber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS) Method; AHERA Pinal Rule, EPA Federal Register (40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987

Sample Identification Analysis Parameters

Proj ect/Site: New Stuyvesant H.S., 345 Chambers St., NY, NY TEM Sample No.: 5775 62377 Exterior & Interior of Buildinc & Roof Date Received: 10/26/01 Grid Openings Analyzed:__ 4

Project Sample No.: 16 Average Grid Opening: 106.00 um

Air Volume: 1944 liters Total Area Analyzed :£^£4 50 mm2

F.l Iter Type: MCE 25 mm diam., Pore Size: 0.45 um Analytical Sensitivity: 22.2 5/mm2 Effective Area:^85mn^ 0.0044 s/cc

FIBROUS PARTICULATES ANALYZED Number Observed CONCENTRATION Total Single Matrix Total. Struct. Filter Air Fibers Bundles Clusters Struct. Struct >=5um Struct/mrr.2 Struct/cc nqm/m3

Chrysotile Asbestos 0 0 0 0 0 0 0.0 0.0000 0

Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0

Ambiguous 0 0 0 0 0 0 0.0 0.0000 0

Total asbestos (includes ambiguous structures) c 0 0.0 0.0000 0 Non-Asbestos 0 0 0 0 c 0 0.0 0.0000 N/A No Identification 0 0 0 0 C 0 0.0 0.0000 N/A

Totals (All Structures) 0 0 0.0 0.0000 N/A The estimated uncertainty of this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED): None detected Amphibole Asbestos Type: None detected

The Analysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the quality specified for the method.

Analyzed by: Report Reviewed by:

Marek Peysakhov Michael A. Gorycki, Ph.D. Director of Electron Microscopy

CITY_21MC100_003082692

NYC-WTC_000293974

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000293974Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000294014

TEM analysis of exterior/interior air at New Stuyvesant H.S., Oct 2001.

Similar indexed content

NYC-WTC_000270668

TEM analysis of asbestos fibers at New Stuyvesant HS with SAED/EDS, Oct 2001.

Similar indexed content

NYC-WTC_000270765

TEM asbestos analysis with SAED/EDS; sample 5748-62070, exterior/interior.

Similar indexed content

NYC-WTC_000270811

TEM asbestos analysis, New Stuyvesant High School exterior/interior, received 10/24/01.

Similar indexed content

NYC-WTC_000270807

TEM asbestos analysis, New Stuyvesant High School exterior/interior, received 10/24/01.

Similar indexed content

Compare copies and versions →