Indoor air quality report, PS 150 M, Feb 2002

Machine-extracted title · confidence 42%

ATC IAQ measurements at PS 150 M prior to re-occupancy, Feb 2002.

NYC-WTC_000289382–000289385
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 26. 2002 Indoor Air Q'uality Assessment Page .3 P. S. 150M_________________ ATC Protect No. 15-19125-0289

Real-Time Environmental Measurements

.RTC collected forty-' (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building w'ere surveyed. These results are described below'.

.Field data sheets are found in Attachment 1. Readings began at 12;00 P.M. and concluded at approximately 1:30 P.M.

I'cmperatiire

Indoor dry bulb temperature measurements ranged from 67.5°F to 75.5°F One (1) of the measurements was above and two (2) were below the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 47.0 to 50.0^F.

.Rt lalive Hiimiditv

The relative humidity indoors ranged from 23.0 to 33.0 percent. Twenty-six of the measurements were below' the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 24.0 to 25.8 percent.

Curhon Dimide Concentrarion

C arbon dioxide concentrations indoors ranged from 535 ppm to 902 ppm. All of the CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (backguound) CO2 concentration was 485 ppm. Therefore, the maximumi acceptable level of COg at this location was 1185 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. TTie school building was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations were 0 to 1 ppm for the interior readings. These concentrations were below the NPAAQS/'ASPIRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm. for all collected readings.

Respirable Particulates (PM?,5/

Respirable particulate concentrations* indoors ranged between 14 pg/m^ to 30 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Tfe average PMp.s concentration for the entire school building was approximately 24 pg/m^. The PM2.5 average concentration was belovc the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration measurements ranged Rom 24 to 32 pg/m^ wifn an average of 28 pg/m^.

CITY_21MC100_0 02954155

NYC-WTC_000289384

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000289384Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →