NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality field report, PS 150M, Feb 2002

Machine-extracted title · confidence 25%

Report of indoor air quality measurements conducted February 8, 2002.

NYC-WTC_000289354–000289357
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan ITbruarx' 11.200.2 Indoor Air Quality Assessment Page 3 P. S. 150M_________________ ATC Proiec-. No. 15-19125-0289

Real-Time Environmental Measurements

ATC collected forty (40) sets of real-time environmental measurements consisting cf thirty ( .3(i ) fi-om inside the school building and ten (10) from outdoors. All three floors ol" the .school building w'cre surveyed. The.se results are described below'.

Field data sheets are found in Attachment 1, Readings began at 11:00 A.M. and concluded at approximately 3:45 P.M.

Temperature

Indoor dry’ bulb temperature measurements ranged from 75.9°F Io 82.2°E. All of the measurements were above the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 53.6 to 55.5' F.

Telciiive Humidity

Idle relative humidity indoors ranged from 14.0 to 24.9 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 15.0 to 16.6 percent.

Carbon Dio:dde Concentration

Carbon dioxide concentrations indoors ranged from 617 ppm to 1350 ppm. Two (2) of the COn measurenients were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 483 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1183 ppm (background level ■+• 700 ppm). Levels abo^c the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator ol' available outside makeup air. The primary source of CO? indoors is occupant respiration. The school Iruilding was occupied during ATC’s assessment.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors were 0 ppms for the interior readings. These concentrations were below’ the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was also 0 ppm for all collected readings.

Respirable Particulates (PM2,§J

Respirable (rarticulate concentrations* indoors ranged between 13 pg/m^ to 34 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Tire average PMp.s concentration for the entire school building was approximately 21 pg/m^. The PM2.5 average concentration was below the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration measurements ranged from 18 to 40 pg/m^ with an average of 28 pg/m^.

CITY_21MC100_002954110

NYC-WTC_000289356

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000289356Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →