Mr. Bernard P. Orlan March 7, 2002 Indoor Air Quality Assessment Page 3 P. S. 150M ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attachment 1. Readings began at 2:00 P.M. and concluded at approximately 3:35 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 68.7°F to 74.1 °F. All of the measurements were within the range of 68 to 75°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements ranged from 42.5 to 43.8‘’F.
Relative Humidity
The relative humidity indoors ranged from 24.3 to 31.5 percent. Twenty-three (23) of the measurements Were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 28.8 to 32.3 percent.
Carbon Dioxide Concentration
Carbon dio>:ide concentrations indoors ranged from 596 ppm to 809 ppm. All of the CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 510 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1210 ppm (background level -F 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. Tlie school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide concentrations were 0 ppm for the interior readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm for all collected readings.
Respirable Particulates (PM2^5)
Respirable fiarticulate concentrations* indoors ranged between 10 ug/m^ to 19 pg/m^. None of the measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 16 pg/m^. The PM2.5 average concentration was beloiv the USEPA recommended concentration of 40 pg/m^ for sensitive individuals / children. The outdoor respirable particulate concentration measurements ranged from 18 to 30 pg/m^ with an average of 20 pg/m^.
CITY_21MC100_0 02954326
NYC-WTC_000289480
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000375533
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375489
Indoor air quality measurements collected Feb 28, 2002 for PS 150M.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300743
ATC provides IAQ evaluation for PS 150M in Mar 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375529
Indoor air quality measurements at P.S. 150M, March 6, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374668
Indoor air quality assessment report for P.S. 150M, Greenwich Street, Apr 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374676
Indoor air quality report for P.S. 150M, Greenwich Street, Apr 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300761
ATC IAQ measurements at PS 150M, March 2002; pre-occupancy monitoring.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374832
IAQ measurements at PS 150M for re-occupancy evaluation, May 23, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300705
ATC IAQ measurements at PS 150M before occupancy, Feb 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300615
ATC indoor air quality measurements at PS 150M prior to re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000410559
Report of IAQ measurements at a NYC school building prior to re-occupancy, March 7, 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374664
Indoor air quality measurements at P.S. 150M, Greenwich Street, Apr 2002.
12 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000300829
IAQ measurements at PS 150M prior to re-occupancy, March 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300655
ATC IAQ field report for PS 150M, Feb 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375481
Indoor air quality measurements collected Feb 11, 2002 for PS 150M.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000194820
Cover letter for indoor air quality measurements collected at PS150M on March 4, 2002, submitted to the Board of Education.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300651
ATC indoor air quality evaluation at PS 150M for re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000375529
Indoor air quality measurements at P.S. 150M, March 6, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000375533
Report of indoor air quality measurements at PS 150M prior to re-occupancy, March 2002.
Similar indexed content
Indoor air quality measurements collected Feb 28, 2002 for PS 150M.
Similar indexed content
NYC-WTC_000300743
ATC provides IAQ evaluation for PS 150M in Mar 2002.
Similar indexed content
NYC-WTC_000375529
Indoor air quality measurements at P.S. 150M, March 6, 2002.
Similar indexed content
NYC-WTC_000374668
Indoor air quality assessment report for P.S. 150M, Greenwich Street, Apr 2002.
Similar indexed content