Mr. Bernard P. Orlan February 6, 2002 Indoor Air Quality Assessment Page 4 P. S, I50M_________________ ATC Project No. 15-19125-0289

’ The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

Tl^OC Concentrations

'fVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSEKVL4TIONS

During this assessment, ATC noted the following: • There was no ccnstruction work going on in the plaza: • The school building was occupied at the time of the assessment; • No smoke odor was detected in the building

FINDINGS

Based on die real-time measurements, the following findings are presented:

1. Concentrations of CO2, CO and TVOCs were within applicable standards and guidelines; 2. None of the PM2,5 measurements were above the NPAAQS of 65 pg/m^ or above the HSEP.A recommended PM2,5 concentration of 40 pg/m-’ for sensitive individuals and childrcri. 3. Two (2) temperature measurements were above the range of 68 to 75® F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. All indoor measurements of relative humidity were below the ASHRAE recommended range of 30 to 60 percent tor occupant comfort.

It is our pleasure to provide these indoor air quality services to the New 'I’ork City Board of Education. If you have any questions about this report, please call (2l2| 353-8280, extension 261 01-212.

Sincerely, Reviewed by: A TC ASSOCJA TES INC.

Andreas C. Andreou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CITY_21MC100_002954084

NYC-WTC_000289345

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000289345Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

IAQ assessment letter, PS150M, Mar 2002

NYC-WTC_000187665

Cover letter from ATC Associates submitting an indoor air quality assessment report for PS150M collected on March 25, 2002.

Similar indexed content

NYC-WTC_000375465

Indoor air quality measurements for P.S. 150M requested by BOE.

Similar indexed content

Compare copies and versions →