ATC indoor air quality measurements at PS 150 M for BOE prior to re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗Indoor air quality measurements conducted for school prior to re-occupancy.
NYC-WTC_000289310–000289313OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan February 1, 2002 Indoor Air Quality Assessment Page 2 P. S. 150M ATC Project No. 15-19125-0289
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not Tepresent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHR.AE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED parameter TARGET LEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75=F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_002954046
NYC-WTC_00028931 1
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000289370
ATC indoor air quality measurements at PS 150 M for BOE prior to re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289478
ATC memo detailing IAQ measurements conducted at PS 150M for BOE re-occupancy.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000214358
Letter transmitting indoor air quality measurement results collected at P.S. 150M on April 8, 2002, for pre-reoccupancy evaluation.
12 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000187665
Cover letter from ATC Associates submitting an indoor air quality assessment report for PS150M collected on March 25, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000187677
Cover letter from ATC Associates submitting an indoor air quality assessment report for PS150M collected on March 18, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253571
ATC IAQ measurements at P.S. 150M for pre-occupancy evaluation by BOE.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374668
Indoor air quality assessment report for P.S. 150M, Greenwich Street, Apr 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289418
IAQ measurements at PS 150 M around March 21-27, 2002.
11 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374708
ATC IAQ measurements at P.S. 150M for BOE air quality assessment, April 26, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289354
Report of indoor air quality measurements conducted February 8, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289398
Indoor air quality measurements conducted at P.S. 150M for BOE prior to occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000300615
ATC indoor air quality measurements at PS 150M prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000289350
Indoor air quality measurements collected for PS 150M; BOE-ordered.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253687
ATC IAQ assessment report for PS 150M for BOE pre-occupancy
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253655
IAQ measurement summary for PS 150M prior to re-occupancy, May 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289458
ATC memo presenting indoor air quality measurements at PS 150M prior to re-occupancy.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289418
IAQ measurements at PS 150 M around March 21-27, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000289370
ATC indoor air quality measurements at PS 150 M for BOE prior to re-occupancy.
Similar indexed content
NYC-WTC_000289478
ATC memo detailing IAQ measurements conducted at PS 150M for BOE re-occupancy.
Similar indexed content
NYC-WTC_000214358
Letter transmitting indoor air quality measurement results collected at P.S. 150M on April 8, 2002, for pre-reoccupancy evaluation.
Similar indexed content
NYC-WTC_000187665
Cover letter from ATC Associates submitting an indoor air quality assessment report for PS150M collected on March 25, 2002.
Similar indexed content
NYC-WTC_000187677
Cover letter from ATC Associates submitting an indoor air quality assessment report for PS150M collected on March 18, 2002.
Similar indexed content