Mr. Bernard P. Orlan May 2, 2002 Indoor Air Quality Assessment Page 2 P. S. 150M ATC Project No. 15-19125-0289
The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy. The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Currently, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:
Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED PARAMETER TARGET LEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO2) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer; 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASHRAE 55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard AIHA = American Industrial Hygiene Association
CITY_21MC100_002893995
NYC-WTC_000253656
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000253671
IAQ measurements collected at PS 150M for BOE pre-occupancy evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253663
IAQ measurement summary for PS 150M school, May 2002, by ATC.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249820
Indoor air quality measurements for PS 150M, prior to occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177974
Letter reporting indoor air quality measurements collected at P.S. 150M on May 2, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374724
ATC IAQ measurements at PS 150M for school building re-occupancy assessment, May 1, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249832
IAQ measurements for PS 150M to evaluate pre-occupancy conditions.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374740
ATC IAQ measurements at PS 150M for pre-occupancy BOE evaluation, May 3, 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253623
ATC IAQ measurements conducted for BOE pre-occupancy evaluation.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249876
ATC reports IAQ measurements at PS 150M, May 15, 2002, to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249808
IAQ measurements for PS 150M to evaluate air quality before building use.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177966
Letter reporting indoor air quality measurements conducted at P.S. 150M to evaluate conditions prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253679
ATC IAQ measurements at P.S. 150M to assess air quality prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000253687
ATC IAQ assessment report for PS 150M for BOE pre-occupancy
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289418
IAQ measurements at PS 150 M around March 21-27, 2002.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289350
Indoor air quality measurements collected for PS 150M; BOE-ordered.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000289458
ATC memo presenting indoor air quality measurements at PS 150M prior to re-occupancy.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253827
ATC IAQ measurements at PS 150 prior to occupancy; data included.
Similarity score 1.000 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000253671
IAQ measurements collected at PS 150M for BOE pre-occupancy evaluation.
Similar indexed content
NYC-WTC_000253663
IAQ measurement summary for PS 150M school, May 2002, by ATC.
Similar indexed content
NYC-WTC_000249820
Indoor air quality measurements for PS 150M, prior to occupancy.
Similar indexed content
NYC-WTC_000177974
Letter reporting indoor air quality measurements collected at P.S. 150M on May 2, 2002.
Similar indexed content
NYC-WTC_000374724
ATC IAQ measurements at PS 150M for school building re-occupancy assessment, May 1, 2002.
Similar indexed content