Appendix 2 Ambient Monitoring and Sampling Protocol

A2.1 Asbestos

To address the concerns regarding the potential of asbestos contamination of the ambient air, daily air testing and analysis was performed, including Saturdays and Sundays, inside and outside the affected school buildings.

A2.2 Ambient Air and Dust Sampling Protocol

The duration of all ambient air samples was approximately 4 hours and the total air volume sampled at each location was approximately 1800 liters.

All ambient air samples collected were analyzed via Transmission Electron Microscopy (TEM) in accordance with the methodology of the AHERA Final Rule.

Results from samples collected each day were reported verbally, no later than Sam the next day, to BOE, UFT, School Principal and the PA consultant. A written report was delivered or faxed by the end of each day.

In the event that any one sample result exceeded (>70 s/mm 2), indicating an unsatisfactory result, the result was reported immediately to the BOE, the UFT, the school principal, the school custodian and the PA consultant. The protocol required said parties to assess the situation and implement the appropriate response action(s).

A2.3 Indoor Air Quality

To address lAQ concerns, each school day (Monday through Friday), the following was performed;

• A visual inspection to assess conditions present in the school at the time of the site visit. • Collect real-time environmental measurements of temperature (T) • Collect real-time environmental measurements of relative humidity (RH) • Collect real-time environmental measurements of carbon dioxide (CO2) • Collect real-time environmental measurements of carbon monoxide (CO) • Collect real-time environmental measurements of total volatile organic compounds (TVOC’s) • Collect real-time environmental measurements of respirable particulates (PM2.5).

A:\B_R«tiofiMngHVAC_R.Ca*eofw.dee 05/IQAn

A2-1

CITY_21MC100_010274217

NYC-WTC_000278830

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000278830Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

PS 89M lab report, 2002 · page 4

NYC-WTC_000250241

Laboratory report page with OCR-garbled content; appears to be environmental test results related to PS 89M.

Similarity score 0.978 (not a probability)

machine-extracted · confidence unavailable · Check page ↗

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →