Stuyvesant High School PM2.5 data memo, Oct 2001

Machine-extracted title · confidence 41%

Memo reviewing PM2.5 data from Stuyvesant High School air quality testing.

NYC-WTC_000277292–000277294
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Stuyvesant High School Page 3 of 3

Windows and doors should be kept closed as much as possible. Based on my recommendations, the Parents’ Association had requested that the Board of Education operate HVAC systems (central air handlers and unit ventilators) on minimum outdoor air, while still maintaining acceptable indoor air quality (as measured with carbon dioxide).

Based on my recommendations, the Parents’ Association also requested that filters with the highest efficiency possible (per manufacturers recommendation) be used in all HVAC equipment. To date the filters in the classroom unit ventilators (approximately 300 units) have not been upgraded.

This afternoon I inspected the perimeter of the school. There was a significant amount of visible dust on West Street a nd the sidewalk/plaza areas on the south and east side of the school. The streets are frequently welted by the Department of Sanitation, however the dust is not removed. When the roadway dries, some of the dust becomes airborne. At the time of my visit it was very windy and dust could be seen blowing in the air. Dust levels were high enough to cause immediate eye irritation. The Chambers Street Bridge was very dusty.

The dust levels in the school are unacceptable and represent a potential health concern. This is of particular concern because the composition of the dust and potential health effects is not completely known. The HVAC filtration system should be upgraded as soon as possible. The school perimeter roads and wall^vays should be HEPA vacuumed and wet cleaned as required to reduce dust levels. The bridge should also be cleaned frequently. If you have any questions, please call.

Sincerely,

Howard A. Bader, P.E. President

( U

CITY_21MC100_009018544

NYC-WTC_000277294

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000277294Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →