NYC 9/11 Public Portal Document
I ATC ASSOCIATES, INC
104 E 25th Street, 10th Floor
New York, NY 10010
I TeL 212-353-8280
Fax 212-353-8306
I
I REPORT DATE:
CLIENT:
08-09-02
Taylor Envoronmental Group, Inc.
0 PROJECT NAME: SCA/Stuy vesant HS
2nd Floor
PROJECT XUArBER: M477-15217/29881
I SAMPLED BY: CUent
I SAMPLE DATE
DATE RECEIVED:
DATE ANALYZED:
08-08-02
08-09-02
08-09-02
I SAMPLE MEDIA:
.ANALYSIS REQUIRED:
Air Samples
Method NIOSH 7032
I analysts restjlts
SAMPLE BATCH SAMPLE DESCRIPTION LEAD DETECTION
I ID NO. CONCENTRATION LIMIT
(Mg/ra’)
I AL-01
AL-02
21025
21025
Rm 250 by Entrance
Rm 251 by Entrance
<2.0
<2.0
2.0
2.0
I AL-03
BLS
21025
21025
Rm 273 by Entrance
Field Blank
<2.0
<1.5 M
2.0
Um
I BL4
AL-04
21025
21025
Field Blank
In Rm 103 Center
<1.5 M
<1.1
Um
1.1
AL-05 21025 In Rm 105 by Door <1.1 1.1
AL-06 21025 In Rm 103 Center <1.3 1.3
AL-07 21025 In Rm 105 fay Door <1.3 1.3
BLl 21025 Field Blank <1.5 pg 1.5 pg
I BL2 21025 Field Blank <1-5 pg 1.5 pg
NOTE 1;
I THE REPORTING LIMIT (RL) IS 3.0 pg
NOTE 2;
At the prescnl lime there sre no regulatory levels or requirement for indoor aiihomc lead in arco samples. However, OSHA bae
established an txtion level of 30 pg/m’ and a pertniaiblc exposure level (PEL) of 50 pg'm’ fcr personal samples.
I NOTE 3:
Blanh units are in pg
NYC-WTC_000275158 CITY_21MC1OO_O111O83OO
OCR can misread numbers and units. Confirm readings against the page image before using them.