Mr. Bernard P. Orlan February 26, 2002 Indoor Air Quality Assessment Page 4 RR89M ATC Project No. 15-19125-0297 individuals and children. The outdoor respirable particulate concentration measurements ranged from 46 to 52 pg/m^ with an average of 49 pg/m3.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

TVOCConc^trzitio^

TVOCs were not detected anywhere inside the building (0.0 ppm). The outdoor TVOC concentration was also 0.0 ppm.

OBSERVATIONS

During this assessment, ATC noted the following: • The school building was occupied at the time of the assessment; • No smoke odor was detected in the building

FINDINGS

Based on the real-time measurements, the following findings are presented:

1. Concentrations of CO and TVOCs were within applicable standards and guidelines; 2. None of the indoor PM2.S measurements were above the NPAAQS of 65 pg/m^ or above the USEPA recommended PM2.5 concentration of 40 pg/m^ for sensitive individuals and children. All of the outdoor PM2.5 measurements were above the USEPA recommended P^^2.5 concentration of 40 pg/m^ for sensitive individuals and children, 3. Fifteen (15) of the temperature measurements were below the range of 68 to 75° F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). 4. Eleven (11) of the indoor measurements of relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. All other measurements were below the ASHRAE recommended range. 5. Four (4) CO2 measurements were above the range recommended by ASHRAE standard 62- 1999. All others were below the maximum concentration.

It is our pleasure to provide these indoor air quality services to the New York City Board of Education. If you have any questions about this report, please call (212) 353-8280, extension 261 01-212.

Sincerely, Reviev/ed by: A TC ASSOCIA TES INC.

AndreasC. Andreou James R. Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division Attachment

CITY_21MC100_003109832

NYC-WTC_000274657

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000274657Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →