Mr. Bernard P. Orlan February 12, 2002
Indoor Air Quality Assessment Page 4
P. S. 89M ATC Project No. 15-19125-0297
asthmatic people and children. The outdoor respirable particulate concentration averaged 6
pg/m^ (A.M.) and 19 pg/m^ (P.M.).
* The measurements made during this assessment were instantaneous readings, the NP/iAQS is
a 24-hour average.
TVOC Concentration
TVOCs were not detected (0.0 ppm) anywhere inside or outside the building.
OBSERVATIONS
During this assessment, ATC noted the following;
• The interior of the building appeared clean and free of dust and debris;
• The school was partially occupied (I.S. 89) at the time of the assessment;
• No smoke odor was detected in the building.
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations of PMgj. CO2, CO and TVOCs were within applicable guidelines.
2. All measurements of temperature, except one, wei e within the ASHRAE-recommended
range.
3. Only three (3) indoor measurements of relative humidity, collected in the morning, were
within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. All
other measurements were below the recommended range.
It is our pleasure to provide these indoor air quality services to the New York City Board of
Education. If you have any questions about this report, please call (212) 353-8280, extension
261 or 212.