NYC 9/11 Public Portal Document
*
ATC Associates
104 East 25 Street New York, NY 10010
Phone:(212) 353-8280 Fax: (212) 353-8306
Attn: Mr. Bernard Orlan Received: 2.TO/O2 5:00:00 PM
N.Y.C. Board of Education
28-11 Queens Plaza North ATC Group#: 6631
Long Island City, NY 11101 Analysis Date: 2/11/02
Fax: (212) 475-4122 Phone: (212) 477-8941
Project: NYC BOE H.S. For Leadership & Public Services
90 Trinity- Place, New York, NY
Asbestos Fiber Analysis by Transmission Electron Microscopy (TEM) Performed
by EPA 40 CFR Part 763 Final Rule (AHERA)
Analytical Asbestos
Aren Nan 'Asbestos Structures Sensitivity Concentration
Sample l^olume Analyzed Asb 0.5f!-S Sfi (S/cc) (S/nim^) (S/cc) Notes
05 1848.00 0.0450 0 None Detected 0 0 0.0046 <22.24 <0.0046
6631 -2
06 1824.00 0.0450 0 None Detected 0 0 0.0047 <22.24 <0.0047
6631 -3
07 1848.00 0.0450 0 None Detected 0 0 0.0046 <22.24 <0.0046
6631 -4
08. 1856.00 0.0450 0 None Detected 0 0 0.0046 <22.24 <0.0046
6631 -5
09 1864.00 0.0450 0 None Detected 0 0 0.0046 <22.24 <0.0046
6631 -6
10 1864.00 0.0450 0 None Detected 0 0 0.0046 <22.24 <0.0046
6631 -7
11 1888.00 0.0450 0 None Detected 0 0 0.0045 <22.24 <0.0045
6631 -8
12 1888.00 0.0450 0 None Detected 0 0 0.0045 <22.24 <0.0045
6631 -9
ROMAN PEYS.AKKQV MICHAEL A. GORYCK.1, Ph.D.
Analyzed .Amroved bv:
Disclaimer. The laboratory is not responsible for data reported in structures/cc. which is dependent on volume oollecied by non-laboratory personnel. This led is only responsible
tor data reponed in structures/mm'. This report may not be reproduced, except in full, without written approval by ATC Associates Inc. This repon may not be used to claim
product endorsement by NVLAP or any other agency of the U.S. Government This reports relates only to the samples reported above. Quality control data (including 95%
confidence limits and laboratory and analysis' accuracy and precision) is available upon request.
Accredited for MVJtP PLM/TEM 4101187-0, NY Stale ELAP #10879