October 19, 2001 ■
Mr. Mohamed Hemida
NEW YORK CITY BOARD OF EDUCATION
Environmental Health & Safety Unit
28-11 Queens Plaza North
Long Island City, New York 11101
RE: WATER SAMPLE ANALYSIS RESULTS
STUYVESANT HIGH SCHOOL
345 CHAMBERS STREET
NEW YORK, NEW YORK
ATC PROJECT NO. 41617-0546
Dear Mr. Hemida:
At the request of the New York City Board of Education (NYCBOE), ATC Associates Inc. (ATC) submitted a water sample that
was collected from a sink tap at Stuyvesant High School (the “Site"). ATC was informed that the sample was collected by a
teacher from Room 705 at an unspecified tap, was then given to the NYCBOE personnel, and subsequently forwarded to ATC.
The sample was reportedly collected on October 11, 2001. ATC submitted the sample to a qualified laboratory for analysis for
RCRA 8 heavy metals.. I
The sample was submitted to New York Environmental & Analytical Laboratories, Inc. for analysis. Laboratory results indicated
that Barium was delected at 2.23 milligrams per liter (mg/l), which is above the New York State Department of Health Drinking
Water Maximum Contaminant Level (MCL) of 1.0 mg/l for this metal. Two additional heavy metals were detected above their
respective MCLs: chromium at 0.11 mg/l (MCL: 0.1 mg/l); and lead at 0.42 mg/l (MCL: 0.015 mg/l).
Further, the method detection limits (MDLs) reported by the laboratory for cadmium and selenium were above the MCLs for
each of these metals. This means that, although the laboratory report indicates that these two metals were undetected to a
specified lower limit (the MDLs), the MDLs for these two substances were above the MCLs. Therefore, it is possible that both
of these metals may be present at concentrations above the MCLs, but not detected by the laboratory. This condition may
have been caused in part by the lack of the required preservative (nitric acid) in the sample container. In addition, the sample
was observed to be highly turbid. When analysis of a-highly turbid water sample is conducted, heavy ..metals are invariably
detected at elevated concentrations due to the composition of the suspended solids, rather than actual heavy metal
contamination in drinking water. Therefore, ATC concludes it is unlikely that this result represents actual drinking water quality
at the Site.
ATC recommends that additional sampling and laboratory analysis be performed at the undisclosed tap under more controlled
■ conditions. Further, the tap should be flushed to remove any visible solids prior to sampling.
The laboratory data is attached. If you have any questions concerning this report, please feel free to call our office.
Sincerely,
ATC ASSOCIATES INC.
Frank Galdun
Technical Director RtenvirtUrankgWataU)oe^47inetals