NYC 9/11 Public Portal Document

Mr. Jim Davis McClier EMTEQUE October 2, 2001 Page two

Summary of results

Asbestos bulk samples

Asbestos has been identified in samples collected from the setback roofs on floors 4, 10, 26, 51, and 52. Thirteen (13) of twenty (23) samples collected on September 30”’ revealed the presence of asbestos. Three (3) of seven (7) samples collected from the 26"' floor roof setback and a single sample collected from the southeast corner of the 25"' floor on September 29"', revealed the presence of asbestos. Asbestos was not present in the samples collected of the dust from within the building with the exception of a single sample collected from the east side of the 16"’ floor which revealed the presence of 1.17% chrysotile asbestos, the EPA’s definition of an asbestos containing material, is a material which contains more than 1% asbestos. In general, multiple dust wipe samples, have been collected from each of the floors with an additional nine (9) samples being collected from the larger setback roofs.

Air sample results

Air samples results are normally compared to two (2) industry standards, the “clean air” standard following asbestos abatement, established by the local regulatory agencies of 0.010 fibers per cubic centimeter (f/cc) and the Permissible Exposure Limit established by the Occupational Safety and Health Administration (OSHA) of 0.1 f/cc. Air sample results from the 36"' floor down revealed results below each of the above referenced standards. Select results from the 37”' floor to the 53’" floor revealed fiber concentrations between both standards, The six (6) samples with the highest fiber concentrations from the upper floors, analyzed via PCM analysis, have been submitted for analysis via TEM, a method of analysis specific to asbestos fibers. Results indicate asbestos fiber levels which are below both of the above referenced standards.

Conclusions

It is EMTEQUE’s opinion that the initial impact to the World Trade Center Structures and possibly, the initial collapsed may have caused the accumulation of bulk debris containing asbestos on the setback roofs and some of this debris may have entered the building immediately below the setback roofs, at the damaged southeast comer, explaining the results from the 25”' floor. On this basis, we would recommend the cleaning of the setback roofs and the areas immediately below the setback roof, on the southeast comer of the building, as an asbestos clean-up project. The balance of the floors can be cleaned as a conventional cleanup. Issues associated with a conventional cleanup are described separately.

With respect to the elevated airborne fiber concentrations on the upper floors, we suspect that the movement of the elevators and the piston effect, along with the natural movement of air in a highrise facility, “chimney affect”, may have caused an accumulation of dust on the upper floors which was noted on the PCM air sampling performed. TEM analysis performed on the samples with the highest fiber concentrations indicate that the dust does not contain asbestos fibers

CITY_21MC100_002821000

NYC-WTC_000268918

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000268918Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000455321

DOH letter explaining asbestos test results in lower Manhattan residences.

Similar indexed content

Compare copies and versions →