Asbestos Inspection Report
Premise No. Inspection Date:
130 Liberty Street 07/21/09
Floor Zip Borough Block Lot Squad # Badge #
Various 10006 1 54 1 1 A062
Inspector Building Type Basis of Inspection Photos Taken
M.Gagnidze F TRU2068MN08 yes
Contractor’s Name Sample Number
LVI Environmental
Address City Sample Number
462 Getty Avenue Clifton
State Zip Phone Sample Number
NJ 07011 973-772-3660
Third Party Air Monitor Owner's Name
TRC Environmental Corp The Lower Manhattan Development Corp.
Address City Address City
1340 Broadway New York One Liberty Plaza New York
State Zip Phone State Zip Phone
NY 10018 212-221-7822 NY 10006 (212) 962-2300
Contact Person Time of Inspection from:
Arnel Javal, Sr. Proj. Mgr/TRC Environmental 9:50 am 10:45 am
I arrived at the premise at 9:50 am. LVI schedule informed that activities include: exterior fapade removal,
setting up scaffolding for fapade work, prep & remove North exterior column tents on 3'“ and 2"'' floors; abate
columns at West Atrium/Vestibule on 2'’‘*floor; break down work area on V floor; demo ducts and conduits,
scrape fireproofing, box out debris in basement.
I used north side hoist to proceed to the 2"“ floor. Three workers were prepping north exterior column tent. I
observed two air monitoring samples # 072109-19 and #072109-20 set up inside and outside decon, but pumps
were not running. Handler supervisor was advised and the cords were plugged in properly and the pumps were
operational. Then I entered the decon, suit up, don respirator and, joined by Supervisor, entered the work area.
2'"' Floor - Three handlers inside the tent were breaking down the bricks around the left side column at the
west Atrium vestibule, spraying the area with amended water, 8 sealed Gaylord boxes were on the floor ready
for load out. After decontamination procedure I suit up, don respirator and using stairs to proceed to the 3"* floor
North exterior column tents work area.
3''“ Floor - Eight workers were inside two tents at the north/west side area of the building. I entered first North !
exterior column tent; handlers were cutting and removing the column aluminum cover, spraying with amended
water. After decontamination I proceeded to the second tent. Workers were in the process of cutting the
aluminum cover. I observed that workers were not spraying the area with amended water; piece of metal was
removed with dry fireproofing on it; filters of three micro traps were dirty; one handler was not wearing hood.
After decontamination procedure I left the decon. Handler Supervisor was advised, and he directed workers to
correct the above discrepancies. I used west side scaffolding ladders, returned to the ground floor and
proceeded to the west side 1®' floor decon to gain the access to the basement A.
Three workers were present for the decon maintenance, cleaning the clean room and organizing shower room.
Negative air pressure on the floor was -0.035.
Basement - 35 Asbestos Handlers were present inside the work area. Workers inside electrical room #2 were
demolishing the machinery, cutting metal from the ceiling, breaking the part of the cinder wall to open the
column. At the pump room workers were demolishing the bottom of the wall, spraying with amended water,
picking up debris and placing into the boxes. Other workers were placing debris info the boxes; preparing and
loading out sprayed boxes through the waste decon, replacing filters of the micro traps. 25 Gaylord boxes were
on the floor ready for load out. Inspection was done on micro trap machines and tents. I observed excessive
water accumulation at the entrance to the waste decon. I took the photos. Then I advised handler supervisor
Jose to clean up the water from the floor for which LVI complied. LVI was advised further that any water
accumulation must be cleaned in a particular area prior to moving handlers to other areas which may prevent
any further leakage in to the clean areas of the basement B.
After following the decontamination procedure I exited the work area.
Inspection was done on ATC trailer.
NOV# Infraction Infraction Infraction Infraction
NOV# Infraction Infraction Infraction Result Code
2
NOV# Infraction Infraction Infraction Supervisor’s Initial
Borough l=Manhattan 2=Bronx 3=Brooklyn 4=Queens 5=Rictimond
Building Type A >6 stories B <6 stories C single family D school E hospital F public owned
Result Code I = Violation Issued 2“No Violation Issued 3=No access 4=Project not started (no NOV)
5=Public Owned Property