Indoor air quality analysis, Oct 2001

Machine-extracted title · confidence 42%

Indoor air quality measurements including temperature, humidity, CO2, CO, VOCs, and particulates.

NYC-WTC_000263550–000263551
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

INDOOU AIR QUALITY ANALYSIS

Project: Newmark & Co. Real Estate, Inc. CTSI Project #.• NY-442-01 Date: October 25, 2001 too Gold Street

LOCATION TEMPERATURE RELATIVE CO2 (PPM) CO (PPM) TOTAL VOC'S TOTAL (’F) HUMIDITY PARTICULATE (RH%) LEVELS in Standard = Standard = Standard = Standard = Standard = Varies Standard= 68-74°F 30-50% 1,000 PPM 9.0 PPM per specific 0.015 mg/m’ parameter Outside 73.8 37.4 339 1.4 ND 0.400 6^ Fl. Section^ 75.5 43.7 602 1.3 ND 0.001 Fl. Section-M 74.4 43.4 615 1.2 ND 0.001 6'" FI. Section-Z 74.1 46.0 673 1.3 ND 0.02 6‘'’ Fl. Section-0 72.2 45.4 558 1.3 ND 0.001 8*" Fl. Section-A 73.2 44.8 556 1.2 ND 0.002 8"’Fl. Section-M 73.5 44.5 676 1.2 ND 0.001 8^ Fl. Section^ 73.7 46.3 711 1.2 ND 0.001 8^ Fl. Section^ 73.3 46.2 625 1.2 ND 0.001 7^” Fl. Section-A 74.8 41.5 580 1.2 ND 0.004 7"' Fl. Section-'M 73.9 42.1 594 1.2 ND 0.005 7*'’ Fl. Section^ 74.4 43.6 644 1.2 ND 0.003 7^ Fl. Section-0 74.3 43.5 631 1.2 ND 0.003 5'^ Fl. Sectioi^ 74.2 39.7 534 1.1 ND 0.004 5“^ Fl. Section-'M 74.2 38.9 539 1.1 ND 0.003 5"’ Fl. SectiorTz" 72.8 43.3 587 1.2 ND 0.002 5“’ Fl. Section-0 72.8 43.1 573 1.1 ND 0.003 Q H °F = degrees Fahrenheit CO = Carbon monoxide CO2 = Carbon dioxide PPM = Parts Per Million RH = Relative humidity ND = Non Detected s o o o I o ND

4Bi Cn

Cn

NYC-WTC_000263550

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000263550Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →