NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

IAQ report, 90 Trinity Place, May 2002

Machine-extracted title · confidence 41%

ATC IAQ measurements collected May 31, 2002 at High School for Leadership & [name].

NYC-WTC_000260517–000260520
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan June 03, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290

Real-Time Environmental Measurements

ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets arc found in the Attachment. Readings were collected in the morning and evening. The results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 71.7 to 82.1. Twenty -seven (27) of the indoor measurements for temperature were above and four (4) measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature ranged from 76.5 to 83.6°F.

Relqtiy^umidity

The relative humidity indoors ranged from 45.5 percent to 52.8 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 60.4 to 68.9 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 648 ppm to 1173 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration v/as 609 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1309 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primar/ source of CO2 indoors is occupant respiration.

Carbon Monoxide Concentration

Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. Ihesc concentrations were below the NP AAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.

Respirable Particuiates (PM2,s)

Respirable particulate concentrations* indoors ranged between 4 pg/m^ to 19 pg/m^ with an average 9 pg/m^- None of the indoor measurements for PM2,5 were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 30 pg/m^ to 74 pg/m- with an average of 51 pg/m^.

CONFIDENTIAL, CITY_21MC100_003464498 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260519

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260519Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000410915

IAQ measurements at 90 Trinity Place; BOE requested assessment of air quality.

Similar indexed content

Compare copies and versions →