Mr. Bernard P. Orlan June 03, 2002 Indoor Air Quality Assessment Page 3 H.S. for Leadership & Public Service (M894) ATC Project No. 15-19125-0290
Real-Time Environmental Measurements
ATC collected one hundred and forty (140) sets of real-time environmental measurements consisting of one hundred and twenty-eight (128) in the school building and twelve (12) outdoors. All fourteen floors of the school were surveyed. Field data sheets are found in the Attachment. Readings were collected in the morning and evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 71.7 to 82.1. Twenty -seven (27) of the indoor measurements for temperature were above and four (4) measurements were below the range of 73 to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55- 1992 during the summer season. The outdoor temperature ranged from 76.5 to 83.6°F.
Relative Humidity
The relative humidity indoors ranged from 45.5 percent to 52.8 percent. All of the indoor measurements for relative humidity were within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity range was 60.4 to 68.9 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 648 ppm to 1173 ppm. All of the indoor measurements for CO2 were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 609 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1309 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors ranged from 0 ppm to 1 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations ranged from 1 ppm to 3 ppm.
Respirable Particulates (PM2j)
Respirable particulate concentrations* indoors ranged between 4 gg/m^ to 19 pg/m^ with an average 9 pg/m^- None of the indoor measurements for PM2.5 were above the NPAAQS of 65 pg/mJ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and the USEPA recommended concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children. The outdoor respirable particulate concentrations ranged from 30 pg/m^ to 74 pg/m- with an average of 51 pg/m^.
CITY_21MC100_003079632
NYC-WTC_000291970
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000399512
June 4, 2002 IAQ measurements update letter to BOE for the school at 90 Trinity Place.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291976
ATC IAQ measurements conducted June 4, 2002 for BOE at the referenced school.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399516
June 5, 2002 IAQ measurement report for Leadership & [name] at 90 Trinity Place.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399496
Indoor air quality report for the referenced NYC BOE school, May 2002.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000292004
ATC IAQ measurements collected June 17, 2002 for the referenced school.
14 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000188385
Memo reporting indoor air quality measurements collected at a school on June 7, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399528
June 10, 2002 IAQ measurements update letter to BOE.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399524
June 7, 2002 IAQ measurements update letter to BOE for the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399504
Correspondence about IAQ measurements at the school, May 30, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000399508
June 3, 2002 IAQ measurement report for 90 Trinity Place.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291942
Indoor air quality measurements at HS Leadership, May 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000291984
ATC IAQ measurements collected June 10, 2002 for the school per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
Page similarity is temporarily unavailable or this page has no indexed vector.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000399512
June 4, 2002 IAQ measurements update letter to BOE for the school at 90 Trinity Place.
Similar indexed content
ATC IAQ measurements conducted June 4, 2002 for BOE at the referenced school.
Similar indexed content
NYC-WTC_000399516
June 5, 2002 IAQ measurement report for Leadership & [name] at 90 Trinity Place.
Similar indexed content
NYC-WTC_000399496
Indoor air quality report for the referenced NYC BOE school, May 2002.
Similar indexed content
ATC IAQ measurements collected June 17, 2002 for the referenced school.
Similar indexed content