Mr. Bernard P. Orlan Apnl 9, 2002
Indoor Air Quality Assessment Page 4
H.S. for Leadersh ip & Public Service ('M894) ATC Project No. 15-19125-0290
concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. Nine (9) of
the twelve (12) instantaneous outdoor measurements were above the USEPA recommended
concentration of 40 pg/m^ for sensitive individuals such as asthmatic people and children.
* The measurements made during this assessment were instantaneous readings, the NIWAQS is
a 24-hour average.
TVOC Concentration
The TVOCs concentrations were 0 ppm inside the building. These concentrations were below
the AIHA guideline for odor control of 1 ppm. The outdoor TVOC concentration was also 0
ppm.
OBSERVATIONS
During this ass essment, ATC noted the following:
• The interior of the building appeared clean and free of dust and debris;
• The building v/as occupied at the time of the assessment;
• No smoke odor was detected in the building;
FINDINGS
Based on the real-time measurements, the following findings are presented:
1. Concentrations: of CO and TVOCs were below applicable standards and guidelines.
2. One hundred and twenty-five (125) indoor measurements for temperature were within and
three (3) measurements were above the range of 68 to 75°F (at 50 percent relative humidity)
recommentied by ASHRAE Standard 55-1992 during the heating season (wintertime
conditions).
3. Sixty-eight (68) of the indoor measurements for relative humidity were below and sixty (60)
measurements were within the ASHRAE-recommended range of 30 to 60 percent for
occupant comfort.
4. Two (2) of the indoor measurements for COy were above the ASHRAE Standard 62-1999
recommended maximum concentration of <700 ppm above the background level. The
highest reading was measured in the gym at 10:59 AM with 27 occupants. Levels above the
recommended maximum do not indicate a health risk. Carbon dioxide measurements are
used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant
respiration.
5. All of the indoor measurements for PM2.5 were below the NPAAQS of 65 pg m- 24-hour
average concen tration of particulate matter 2.5 micrometers or less in aerodynamic diameter
and the USEP/V recommended concentration of 40 pg/m^ for sensitive individuals such as
asthmatic people and children. Four (4) of the outdoor measurements for PM2 5 were above
the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5
micrometers or less in aerodynamic diameter. Nine (9) of the twelve (12) instantaneous
outdoor measurements were above the USEPA recommended concentration of 40 pg/m^ for
sensitii^e individuals such as asthmatic people and children.