Indoor air quality report, HS Leadership, Mar 2002

Machine-extracted title · confidence 38%

ATC IAQ measurements at High School for Leadership & [name], 90 Trinity Place, March 2002 for BOE program.

NYC-WTC_000260033–000260037
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

104 East 25th St., 10th Floor New York, New York 10010 www.atc-enviro.com 212.353.8280 Fax 212.353.8306 ASSOCIATES INC.

March 22, 2002

Mr. Bernard P. Orlan Director, Environmental Elealth & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101-4008

Re: Indoor Ait Quality Assessment High School for Leadership & Public Service (M894) 90 Trinity Place New York, New York 10006 ATC Project No. 15-19125-0290

Dear Mr. Orlan:

ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on March 21, 2002, at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained.

SCOPE OF W ORK

ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity’, carbon dioxide i CO,) and carbon monoxide (CO).

Total volatile organic compounds (TVOCs) and respirable particulates were also measured.

Manana Medinets, Environmental Technician, of ATC’s New York City office, conducted the assessment. ATC’s findings are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.

ATC measured temperature, relative humidity, CO, and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc.

ATC measured concentrations of respirable particulates (PM2.5) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.

ATC measured concentrations of TVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).

The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy.

CONFIDENTIAL, CITY_21MC100_003463750 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000260033

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000260033Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000370534

Indoor air quality measurements collected March 21, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000180183

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in March 2002.

Similar indexed content

NYC-WTC_000370496

Indoor air quality measurements collected March 13, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000259977

IAQ measurements collected Mar 13, 2002 for BOE

Similar indexed content

Compare copies and versions →