ATC collected IAQ data for June 26, 2002 at the school, per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗ATC indoor air quality measurements at the referenced school, June 26, 2002.
NYC-WTC_000259547–000259550OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. E emard P. Orlan June 27,2002 Indocr Air Quality Assessment Page 2 tU^i)f Economics and Finance (My3) ATC Project No. 15-19125-0291
The results of the sampling represent conditions found on the dates of the survey and may not represent conditions found at other times. The information presented in this report should be used ay the BOE as a guide to assess the need for further improvements in current indoor air quality control activities.
EVALUATION CRITERIA
Curreitly, there are no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guide' ines cited in the following publications:
l^entilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).
Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one, some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.
TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED
PARAMETER TARGET LEVEL Ipl
Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO;.) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO) USEPA NPAAQS) Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (p.g/m3) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals Tem-jerature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Rela ive Humidity 30 - 60 % ASHRAE 55 Tota Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPyi = United States Environmental Protection Agency NPAA QS == National Primary Ambient-Air Quality Standard AIIIA = American Industrial Hygiene Association
CONFIDENTIAL, CITY_21MC100_003463012 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259548
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000396735
ATC collected IAQ data for June 26, 2002 at the school, per BOE request.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259539
ATC indoor air quality measurements at the High School of Economics and Finance, June 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259543
ATC indoor air quality measurements at the referenced school, June 25, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259515
ATC IAQ measurements report for June 13, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259523
ATC IAQ measurements report for June 18, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259531
ATC IAQ measurements report for June 20, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223596
Report of indoor air quality measurements collected at the High School of Economics and Finance on June 25, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259535
ATC indoor air quality measurements at High School of Economics and Finance, June 21, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000385115
ATC IAQ measurements collected June 18, 2002 for BOE at the High School of Economics and Finance.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259475
ATC indoor air quality measurements report for May 29, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396645
ATC IAQ measurements collected May 24, 2002 for IAQ assessment.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000223592
Report of indoor air quality measurements collected at the High School of Economics and Finance on June 24, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.997
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000259539
ATC indoor air quality measurements at the High School of Economics and Finance, June 24, 2002.
Similarity score 0.996 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259184
ATC Associates report on IAQ measurements taken April 12, 2002 at the school for BOE review.
Similarity score 0.995 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259515
ATC IAQ measurements report for June 13, 2002 at the school.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259300
IAQ measurements collected May 1, 2002 for BOE program.
Similarity score 0.994 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000179990
Letter from ATC Associates reporting indoor air quality measurements collected at a school on April 9, 2002.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259145
Report of IAQ measurements at 100 Trinity Place for BOE program, March 2002.
Similarity score 0.993 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC collected IAQ data for June 26, 2002 at the school, per BOE request.
Similar indexed content
NYC-WTC_000259539
ATC indoor air quality measurements at the High School of Economics and Finance, June 24, 2002.
Similar indexed content
NYC-WTC_000259543
ATC indoor air quality measurements at the referenced school, June 25, 2002.
Similar indexed content
ATC IAQ measurements report for June 13, 2002 at the school.
Similar indexed content
ATC IAQ measurements report for June 18, 2002 at the school.
Similar indexed content