NYC Law Department release
Independent mirror · updated as the City releases more · v1.3.2
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor Air Quality Report, April 9, 2002, NYC School

Machine-extracted title · confidence 98%

Letter from ATC Associates reporting indoor air quality measurements collected at a school on April 9, 2002.

NYC-WTC_000179990–000179993
Page image
Scanned page image, NYC-WTC_000179991
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan April 10. 2002 Indooi Air Quality .Assessment Page 2 ITS. of Economics and Finance (M833) ATC Proiect No. 15-19125-0291 The rt suits of the sampling represent conditions found on the dates of the survey' and may not represent conditions found at other times. The information presented in this report should be used by the BOE as a guide to assess the need for further improvements in current indoor air quality' control activities.

EVALUATION CRITERIA

Currently, there are no regulatory' standards for indoor air quality in non-industrial buildings. such £S offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

Ventilation for Acceptable Indoor Air Quality (ASHIL4E 62-1999), American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992j: Industrial Hygienists Guide to Indoor Air Quality Investigations (1993). American Industrial Hygiene Association (AIHA).

Table 1 lists target guidelines for the parameters that ATC evaluated during this investigation. Meeting one. some, or all of the listed values does not assure that acceptable indoor air quality will be achieved at all times.

TABLE 1 TARfJET GUIDEIJNES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED

PARAMETER TARGET LEVEL AGENCY OR ORGANIZATION Carbon Dioxide <700 parts per million (ppm) ASHRAE 62 (CO;>) above background level Carbon Monoxide 9 ppm ASHRAE 62 (adopted from (CO- USEPA NP/iAQS) Resp irable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 ug im' 24-hour average USEPA - Recommendation for children / sensitive individuals Temperature Summer: 73-79°F at 50% RH ASHRAE 55 Winter: 68-75°F at 50% RH Relative Humidity 30 - 60 % ASIIRAE55 Total Volatile Organic Compounds 1 ppm AIHA (TVOC) USEPA = United States Environmental Protection Agency NPAjAQS = National Primary Ambient-Air Quality Standard AIHA =- American Industrial Hygiene Association

CONFIDENTIAL, CITY_21MC100_003462199 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000179991

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000179991Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000179972

Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 8, 2002.

Similar indexed content

NYC-WTC_000180188

Cover letter from ATC Associates to the NYC Board of Education submitting indoor air quality measurements for 90 Trinity Place in April 2002.

Similar indexed content

NYC-WTC_000179985

Letter from ATC Associates reporting indoor air quality measurements collected at a school on March 21, 2002.

Similar indexed content

Compare copies and versions →