Mr. Bernard P. Orlan June 12,2002 Indoor Air Quality Assessment Page 3 H.S. of Economics and Finance (M833)_______ ATC Project No. 15-19125-0291 Real-Time Environmental Measurements
ATC collected one hundred and six (106) sets of real-time environmental measurements consisting of ninety-four (94) inside the school building and twelve (12) outdoors. Field data sheets are found in the Attachment. Readings were collected between morning to evening. The results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 77.0 °F to 82.6 °F. Sixty-seven (67) of the indoor measurements for temperature were above the range of 73 °F to 79°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the summer season. The outdoor temperature measurements ranged from 80.2 °F to 86.0 °F.
RelgtiyeHumidify
The relative humidity indoors ranged from 42.1 percent to 59.5 percent. All the indoor measurements for relative humidity were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity ranged from 60.6 to 65.0 percent.
CarbonDipxideConcentrqtion
Carbon dioxide concentrations indoors ranged from 478 ppm to 1670 ppm. Thirteen (13) of the indoor measurements for CO2 were above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO2 concentration was 470 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1170 ppm (background level + 700 ppm). The highest concentration (1670 ppm) was recorded on the floor staircase A around 12:57 PM with 0 occupants. Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration.
Carbon MnnoxideConcentration
Carbon monoxide concentrations indoors ranged from 1 ppm to 2 ppm. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentrations were 1 ppm for all readings.
Respirable Particulates (PM2 §)
Respirable particulate concentrations* indoors ranged between 6 pg/m^ to 130 pg/m^ with an average of 21 pg/m^- Eight (8) of the indoor measurements for respirable particulates were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter and nine (9) of the indoor measurements were above the USEPA recommended concentration of 40 pg/m^ for sensitive individuals and children. The respirable concentrations outdoors ranged between 126 pg/m^ to 186 pg/m^ witb an average of 150 pg/m^ •
CONFIDENTIAL, CITY_21MC100_003462837 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000259509
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000259401
ATC indoor air quality measurements collected May 14, 2002.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396699
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259495
ATC IAQ measurements report for June 5, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396531
Measurements collected May 14, 2002; BOE monitoring.
14 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396474
Indoor air quality measurements collected May 8, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259523
ATC IAQ measurements report for June 18, 2002 at the school.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384246
Indoor air quality measurements collected on March 22, 2002 at HS Economics & Finance.
13 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396683
IAQ measurements collected Jun 5, 2002 for school IAQ maintenance check.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396488
Indoor air quality measurements collected May 9, 2002 for BOE.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000384900
May 9-10 IAQ measurements at the school, part of BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259286
May 1, 2002 IAQ measurements for BOE program.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259145
Report of IAQ measurements at 100 Trinity Place for BOE program, March 2002.
14 shared non-person entities · 1 shared topics · similarity 0.998
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000396699
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396687
ATC reports IAQ measurements at High School of Economics and Finance, June 2002, per BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396695
ATC IAQ measurements conducted June 10, 2002 for BOE program to maintain acceptable IAQ.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259499
ATC IAQ measurements report for June 6, 2002 at the school.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000396735
ATC collected IAQ data for June 26, 2002 at the school, per BOE request.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000259483
ATC IAQ report documenting measurements collected June 3, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Machine-extracted building matches; verify each source. Buildings, never households.
Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
ATC indoor air quality measurements collected May 14, 2002.
Similar indexed content
ATC IAQ measurements collected June 11, 2002 at the school for BOE IAQ monitoring.
Similar indexed content
ATC IAQ measurements report for June 5, 2002 at the school.
Similar indexed content
Measurements collected May 14, 2002; BOE monitoring.
Similar indexed content
Indoor air quality measurements collected May 8, 2002 for BOE.
Similar indexed content