NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 4 pages

Indoor air quality report, M833, Feb 2002

Machine-extracted title · confidence 42%

IV notes on IAQ measurements collected for BOE program, Feb 2002.

NYC-WTC_000257035–000257038
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr Bernard P Orlan March 1, 2002 Indoor Air Quality Assessment Page 4 HS of Economics and Finance fM8331 ATC Protect No 15-19125-0291

TVOC Concentration

TVOCs were not detected anywhere inside the building (0 0 ppm) The outdoor TVOC concentration was also 0.0 ppm

OBSERVATIONS

During this assessment, ATC noted the following • The interior of the building appeared clean and free of dust and debris, • The building was occupied at the time of the assessment, • No smoke odor was detected in the building,

FINDINGS

Based on the real-time measurements, the following findings are presented

1. Concentrations of respirable particulates, TVOCs, and carbon monoxide were below applicable standards and guidelines. 2. One (1) of the measurements for carbon dioxide was above the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level 3. One hundred twenty-eight (128) measurements for relative humidity were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. Five (5) of the relative humidity measurements were within the ASHRAE recommended range of 30 to 60 percent for occupant comfort 4. One hundred twenty (120) temperature measurements were below the range of 68 to 75°F (at 50 percent relative humidity recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions)

It is our pleasure to provide these indoor air quality services to the New' York City Board of Education If you have any questions about this report, please call (212) 353-8280, extension 261 or 212

Sincerely, Reviewed by A TC ASSOCIA T£S INC.

James R Cohn, CIH, CSP Senior Project Manager Regional Manager Industrial Hygiene Division

Attachment

CONFIDENTIAL, CITY_21MC100_003459436 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000257038

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000257038Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000297790

ATC IAQ report for Feb 13, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000297808

ATC indoor air measurements report for February 14, 2002 at the school.

Similar indexed content

Compare copies and versions →