Indoor air quality report, 90 Trinity Place, Feb 2002

Machine-extracted title · confidence 42%

ATC report on indoor air quality measurements at a NYC high school site, conducted Feb 7, 2002.

NYC-WTC_000256872–000256875
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

104 East 25th St New York, New York 10010 wwwatc-enviro com 212 353 8280 Fax 212 353 8306 ASSOCIATES INC

February 8, 2002

Mr Bernard P. Orlan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101-4008

Re: Indoor Air Quality Assessment High School for Leadership & Public Service (M894) 90 Trinity Place New York, New York 10006 ATC Project No. 15-19125-0290

Dear Mr Orlan-

ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on February 7, 2002, at the referenced school The New York City Board of Education (BOE) requested these measurements as part of a program to detennme if acceptable indoor air quality is being maintained,

SCOPE OF WORK

ATC conducted this evaluation to assess the basic parameters of temperature, relative humidity, carbon dioxide (COj) and carbon monoxide (CO)

Total volatile organic compounds (TVOCs) and respirable particulates were also measured

Darnell Nehlich, Industrial Hygienist, of ATC’s New York City office, conducted the assessment ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment

ATC measured temperature, relative humidity, COj and CO with a Q-Trak® Model 8551, manufactured by TSI, Inc

ATC measured concentrations of respirable particulates (PM2,5) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc

ATC measured concentrations of TVOCs using a RAE Systems, Inc MiniRAE® photoionization detector (PID).

The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and sampling and analytical accuracy

CONFIDENTIAL, CITY_2IMCI00_007741177 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000256872

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000256872Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000297757

ATC quality report for IAQ measurements at a NYC high school in Feb 2002.

Similar indexed content

NYC-WTC_000297790

ATC IAQ report for Feb 13, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000297826

ATC report of IAQ measurements collected Feb 15, 2002 at the referenced school.

Similar indexed content

NYC-WTC_000297808

ATC indoor air measurements report for February 14, 2002 at the school.

Similar indexed content

Compare copies and versions →