NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan February 19, 2002 Indoor Air Quality Measurements Page 2 Stuyvesant High School (M477) ATC Project No. 15-19125-0246 EVALUATION CRITERIA

Currently, there are_ no regulatory standards for indoor air quality in non-industrial buildings, such as offices and schools. For the real-time data collected, ATC uses the commonly accepted guidelines cited in the following publications:

Ventilation for Acceptable Indoor Air Quality (ASHRAE 62-1999), Amencan Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE); Thermal Environmental Conditions for Human Occupancy (ASHRAE 55-1992); Industrial Hygienists Guide to Indoor Air Quality Investigations (1993), American Industrial Hygiene Association (AIHA).

Table 1 lists target guidelines for respirable particulates that ATC evaluated during this investigation. Meeting the listed values does not assure that acceptable indoor air quality will be achieved at all times.

TABLE 1 TARGET GUIDELINES FOR INDOOR AIR QUALITY PARAMETERS EVALUATED -i

Respirable 65 micrograms per cubic meter USEPA NPAAQS Particulates (PM2.5) of air (pg/m^) 24-hour average 40 pg/m^ 24-hour average USEPA - Recommendation for children / sensitive individuals USEPA = United States Environmental Protection Agency NPAAQS = National Primary Ambient-Air Quality Standard

Real-Time Environmental Measurements

ATC collected one hundred and one (101) sets of real-time environmental measurements •consisting of ninety-nine (99) in the school building and two (2) outdoors. All ten floors of the school were surveyed. These results are described below.

Field data sheets are found in Attachment 1. Readings began at 7:50 A.M. and concluded after 11:25 A.M.

Respirable Particulates (PM2,5)

Respirable particulate concentrations* indoors ranged between 3 pg/m^ to 14 pg/m^ with an average of approximately 6 pg/m^. None of the measurements were above the NPAAQS of 65, pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommendation of 40 pg/m^ for sensitive individuals and children. The outdoor respirable particulate concentrations were 26 and 28 pg/m^.

In addition to higher efficiency rating filters on their HVAC units, portable High Efficiency Particulate Air (HEPA) purifiers were placed in Rooms 327, 333, 638 and 740. The PM2.5 concentration range for these rooms was 4 -6 pg/m^ with an average of approximately 5 pg/m^.

CONFIDENTIAL, CITY_21MC100_003457908 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000256092

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000256092Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000256103

ATC memo reporting respirable particulate measurements at Stuyvesant High School (Feb 19, 2002).

Similar indexed content

Compare copies and versions →