ATC memo, Stuyvesant HS IAQ, Jan 2002

Machine-extracted title · confidence 42%

ATC memo detailing IAQ measurements at Stuyvesant High School.

NYC-WTC_000255777–000255780
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

104 East 25th Street

ITC ASSOCIATES INC. New York. New York' 10010 www.atc-enviro.com 212.353.8280 Fax 212.353.8306

January 7, 2002'

Mr. Bernard P. Orfan Director, Environmental Health & Safety New York City Board of Education 28-11 Queens Plaza North Long Island City, NY 11101-4008

Re: Indoor Air Quality Assessment Stuyvesant High School (M477) 345 Chambers Street New York, New York 10007 ATC Project No. 15-19125-0246

Dear Mr. Orlan:

ATC Associates Inc. (ATC) is pleased to provide this report of indoor air quality (lAQ) measurements collected on January 4, 2002, at the referenced school. The New York City Board of Education (BOE) requested these measurements as part of a program to determine if acceptable indoor air quality is being maintained.

SCOPE OF WORK

ATC conducted this evaluation to assess the basic parameters-of temperature, relative humidity, carbon dioxide (CO,) and carbon monoxide (CO).

Total volatile organic compounds (TVOCs) and respirable particulates were also measured.

Jimmy Choy, Industrial Hygienist, of ATC’s New York City office, conducted the assessment.. ATC’s findings and conclusions are based on a visual inspection, real-time environmental measurements and conditions present in the school at the time of the assessment.

ATC measured temperature, relative humidity, CO, and CO with a Q-Trak® Model 8551, .mam-.factured by TSI, Inc.

ATC measured concentrations of respirable particulates (PMnj) with a Dust-Trak® Aerosol Monitor Model 8520, manufactured by TSI, Inc.

ATC measured concentrations ofTVOCs using a RAE Systems, Inc. MiniRAE® photoionization detector (PID).

The assessment was performed consistent with generally accepted indoor air quality assessment practices. As with all such assessments, there were inherent limitations created by constraints of time, operational and work practice variability, variations in indoor air quality parameters and

CONFIDENTIAL, CITY_21MC1OO_OO3457516 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000255777

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000255777Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →