NYC-WTC_000249792
Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
NYC-WTC_000249796–000249799OCR status: ok · source: pdftotext
NYC 9/11 Public Portal Document
Mr. Bernard P. Orlan April 29, 2002 Indoor Air Quality Assessment Pages P. S. 150M ATC Project No. 15-19125-0289
Real-Time Environmental Measurements
ATC collected forty (40) sets of real-time environmental measurements consisting of thirty (30) from inside the school building and ten (10) from outdoors. All three floors of the school building were surveyed. These results are described below.
Field data sheets are found in Attaehment 1. Readings began at 11:50 A.M. and concluded at approximately 1:16 P.M.
Temperature
Indoor dry bulb temperature measurements ranged from 69.7°F to 71.9°F. All of the measurements were below the range of 73 to 79°F (at 50 percent relative humidity) as recommended by the ASHRAE Standard 55-1992 during the heating season (summertime conditions). The outdoor temperature measurements ranged from 62.8°F to 65.6°F.
Relative Humidity
The relative humidity indoors ranged from 23.3 to 25.9 percent. All of the measurements were below the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. The outdoor relative humidity measurements ranged from 21.2 to 21.6 percent.
CarhonJ)ioxideCoricentration
Carbon dioxide concentrations indoors ranged from 491 ppm to 1016 ppm. All of the CO2 measurements were within the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The maximum outdoor (background) CO2 concentration was 469 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1169 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator of available outside makeup air. The primary source of CO2 indoors is occupant respiration. The school building was occupied during ATC’s assessment.
Carbon Monoxide Concentration
Carbon monoxide indoor concentrations were 1 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration were also 1 ppm for all collected readings.
Respirable Particulates (PM2_5) ppm.
Respirable particulate concentrations* indoors ranged between 17 pg/m^ to 25 pg/m^. None of the indoor measurements were above the NPAAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter or the USEPA recommendation of 40pg/m3 for sensitive individuals and children. The average PM2.5 concentration for the entire school building was approximately 21 pg/m^. The outdoor respirable particulate concentration measurements ranged from 14 to 17 pg/m3 with an average of 16 pg/m^.
CONFIDENTIAL, CITY_21MC100_005759642 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008
NYC-WTC_000249798
OCR can misread numbers and units. Confirm readings against the page image before using them.
Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.
NYC-WTC_000249792
Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249804
Report of IAQ measurements at PS 150M to assess air quality prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249820
Indoor air quality measurements for PS 150M, prior to occupancy.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249808
IAQ measurements for PS 150M to evaluate air quality before building use.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000177974
Letter reporting indoor air quality measurements collected at P.S. 150M on May 2, 2002.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249876
ATC reports IAQ measurements at PS 150M, May 15, 2002, to evaluate air quality before re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 1.000
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249784
ATC IAQ measurements report for PS 150M, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249912
ATC IAQ measurements at PS 150M, May 23–24, 2002, prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249931
ATC IAQ measurements at PS 150M, May 31, 2002, prior to re-occupancy.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249832
IAQ measurements for PS 150M to evaluate pre-occupancy conditions.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249768
ATC IAQ measurements report for PS 150M, April 2002.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000253855
ATC IAQ measurements at PS 150M for pre-occupancy review.
13 shared non-person entities · 1 shared topics · similarity 0.999
machine-extracted · confidence unavailable · Check page ↗No available related records indexed in this group.
Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.
NYC-WTC_000177974
Letter reporting indoor air quality measurements collected at P.S. 150M on May 2, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249832
IAQ measurements for PS 150M to evaluate pre-occupancy conditions.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249792
Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249808
IAQ measurements for PS 150M to evaluate air quality before building use.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000374740
ATC IAQ measurements at PS 150M for pre-occupancy BOE evaluation, May 3, 2002.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗NYC-WTC_000249804
Report of IAQ measurements at PS 150M to assess air quality prior to re-occupancy.
Similarity score 0.999 (not a probability)
machine-extracted · confidence unavailable · Check page ↗Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.
NYC-WTC_000249792
Report of IAQ measurements at PS 150M, requested to evaluate air quality before re-occupancy.
Similar indexed content
NYC-WTC_000249804
Report of IAQ measurements at PS 150M to assess air quality prior to re-occupancy.
Similar indexed content
NYC-WTC_000249820
Indoor air quality measurements for PS 150M, prior to occupancy.
Similar indexed content
NYC-WTC_000249808
IAQ measurements for PS 150M to evaluate air quality before building use.
Similar indexed content
NYC-WTC_000177974
Letter reporting indoor air quality measurements collected at P.S. 150M on May 2, 2002.
Similar indexed content