Asbestos TEM analysis, Stuyvesant H.S., Oct 2001

Machine-extracted title · confidence 42%

TEM asbestos analysis for Stuyvesant High School; AHERA/PART 763 references.

NYC-WTC_000248496
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

ATC Environmental, Inc. 104 East 25th Street New York, New York 10010 N.Y.C. Board of Education Approved N.Y. State ELAP #10879 28-11 Queens Plaza North ACCREDITED NVLAP Lab Code # 1187 Long Island Coty, NY 11101 Report Date: 10/05/01

ASBESTOS FIBEP. ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM) With Fiber Identificdticn by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy {EDSi Method; ?iHERA Final Rule, SPA Federal Register (40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987

Sample Identification Analysis Parameters

Proj ect/Si te: Stuyvesant H.S., 345 Chambers St., NY, NY TEM Sample No.: 5509 60050 Floor^l^DO Date Received: 10/05/^01 Grid Openings Analyzeci:__ 4

Project Sample No. : .0 -10/5-4 3 Average Grid Opening: 106.00 um

Air Volume: 1872 liters! Total Area Analyzed ; 0^^4.£0 n^

Filter Type: MCE 25 mmclieni., Pore Size: 0.45 um Analytical .Sensitivity: 22.2 s/m-n2 Effective Aren: 385mn^ 0 . 0046 s/cc

FIBROUS PARTICULATES ANALYZED Number Observed CONCENTRATION Total Single Matrix Total. Struct. Filter Air Fibern Btmdles Clusters Strkict. Struct > = 5um Struct/mm2 Struct./cc ncjm/m3

Chrysotil? Asbestos 0 0 0 0 0 0 0.0 0. Qono 0

Amphibole Asbestos 0 0 0 0 0 c 0.0 0.0000 G

Ambiguous 0 0 0 0 0 0 0.0 0 . 0000 0

Total asbestos (includes an-bi-guous structures) 0 0 C .0 0.0000 0 Non-Asbestos 0 0 0 0 0 0 0.0 0.0000 N/'A No Identitication 0 0 0 0 0 0 0,0 0.0000 N/A

Totals {All Structures) 0 0 0.0 0.0000 N/A The estimated uncertainty cf this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED): None detected Amphibole Asbestos Type: None detected

The Analysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the quality specified for the method.

Analyzed by: Report Reviewed by;

Michael A. Gorycki, Ph.D. Michael A. Gorycki, Ph.D. Directoi' of Electron Microscopy

CONFIDENTIAL, CITY_21MC100_003473596 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000248496

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000248496Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →