Indoor air quality report, P.S. 89M, Jan 2002

Machine-extracted title · confidence 35%

ATC Associates reports IAQ measurements at P.S. 89M for NYC BOE, January 2002.

NYC-WTC_000245321–000245324
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

Mr. Bernard P. Orlan January 22, 2002 Indoor Air Quality Assessment Page 3 P, S. 89 (Manhattan) ATC Project No. 15-19125-0297

Real-Time Environmental Measurements

ATC collected sixty-one (61) sets of real-time environmental measurements consisting of fifty- nine (59) from inside the school building and four (2) outdoors. Ah five floors of the school were surveyed. These results are described below.

Temperature

Indoor dry bulb temperature measurements ranged from 67.6 °F to 74.4 °F. Seven (7) measurements were below the range of 68 to 75°F (at 50 percent relative humidity) recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions). The outdoor temperature measurements were 42.2 °F.

Relative Humidity

The relative humidity indoors ranged from 22.4 percent to 30.8 percent. Only one (1) measurement was within the ASHRAE-recommended range of 30 to 60 percent for occupant comfort. All other measurements were below the recommended range. The outdoor relative humidity ranged from 49.3 to 50.0 percent.

Carbon Dioxide Concentration

Carbon dioxide concentrations indoors ranged from 431 ppm to 509 ppm. All CO? measurements were below the ASHRAE Standard 62-1999 recommended maximum concentration of <700 ppm above the background level. The outdoor (background) CO? concentrations were 469 and 470 ppm. Therefore, the maximum acceptable level of CO2 at this location was 1170 ppm (background level + 700 ppm). Levels above the recommended maximum do not indicate a health risk. Carbon dioxide measuremenls are used as an indicator of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school building during ATC’s assessment was not occupied.

CaHionMo^HdeCvncentration

Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0 ppm.

Respirable Particulates <'PM2,5)

Respirable particulate concentrations* indoors ranged between 29 pg/m^ to 61 pg/m^. All measurements were below the NP.AAQS of 65 pg/m^ 24-hour average concentration of particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5 concentration for the entire school building was approximately 40 pg/mA The outdoor respirable particulate concentrations were 70 and 71 pg/m^.

* The measurements made during this assessment were instantaneous readings, the NPAAQS is a 24-hour average.

CONFIDENTIAL, CITY_21MC100_003471718 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000245323

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000245323Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

Compare copies and versions →