Mr. Bernard P. Orlan January 22, 2002
Indoor Air Quality Assessment Page 3
P. S. 89 (Manhattan) ATC Project No. 15-19125-0297
Real-Time Environmental Measurements
ATC collected sixty-one (61) sets of real-time environmental measurements consisting of fifty-
nine (59) from inside the school building and four (2) outdoors. All five floors of the school
were surveyed. These results are described below.
Temperature
Indoor dry bulb temperature measurements ranged from 67.6 °F to 74.4 °F. Seven (7)
measurements were below the range of 68 to 75°F (at 50 percent relative humidity)
recommended by ASHRAE Standard 55-1992 during the heating season (wintertime conditions).
The outdoor temperature measurements were 42.2 °F.
Relative Humidity
The relative humidity indoors ranged from 22.4 percent to 30.8 percent. Only one (1)
measurement was within the ASHRAE-recommended range of 30 to 60 percent for occupant
comfort. All other measurements were, below the recommended range. The outdoor relative
humidity ranged from 49.3 to 50.0 percent.
Carbon Dioxide Concentration
Carbon dioxide concentrations indoors ranged from 431 ppm to 509 ppm. All CO2
measurements were below the ASHRAE Standard 62-1999 recommended maximum
concentration of <700 ppm above the background level. The outdoor (background) CO2
concentrations were 469 and 470 ppm. Therefore, the maximum -acceptable level of COo at this
location was 1170 ppm (background level + 700 ppm). Levels above the recommended
maximum do not indicate a health risk. Carbon dioxide measurements are used as an indicator
of available outdoor air. The primary source of CO2 indoors is occupant respiration. The school
building during ATC’s assessment was not occupied.
Carbon Monoxide Concentration
Carbon monoxide concentrations indoors were 0 ppm for all readings. These concentrations
were below the NPAAQS/ASHRAE guideline of 9 ppm. The outdoor CO concentration was 0
ppm-
Respirable Particulates (PM2 jy
Respirable particulate concentrations* indoors ranged between 29 pg/m^ to 61 pg/m^. All
measurements were below the NPAAQS of 65 pg/m3 24-hour average concentration of
particulate matter 2.5 micrometers or less in aerodynamic diameter. The average PM2.5
concentration for the entire school building was approximately 40 pg/m^. The outdoor
respirable particulate concentrations were 70 and 71 ug/m3.
* The measurements made during this assessment were instantaneous readings, the NPAAQS is
a 24-hour average.