NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 1 page

TEM report, New Stuyvesant HS facility

Machine-extracted title · confidence 60%

TEM analysis report with asbestos TEM, SAED and EDS details for NYCHA project.

NYC-WTC_000244714
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

ATC Environmental, Inc. 104 East 25th Street New York, New York 10010

N.Y.C. Board of Education Approved N.Y. State ELAP #10879 28-11 Queens Plaza North ACCREDITED NVLAP Lab Code # 1187 Long Island City, NY 11101 Report Date: lO/22/Ol

ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM) With Fiber Identification joy Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS! Method: AIERA Final Rule, I PA Federal Register i40 CFR, Part 763;, Vol. 52, No. 210, October 30, 1987

Sample i cat ion Analysis Parameters

Project/Site; New Stuyvesant H.S., 345 Chambers St., NY, NY TEM Sample No.: fiia22 Exterior & Interior of Building & Roof Date Received:10/21/01 Grid Openings Analyzed:__4

Project S.imple No. :_1 Average Grid Opening; 106.00 urn

Air Volume: 192S liters Total Area Analyzed 0450 mm2

Filter Ty}>e ; MCE 25 min diani-. Pore Size: 0.45 uin Analytical Sensitivity: 22.2 s/nnn2 Effective Are®: 385 mm2 0. 0044 s/cc

FIBROUS PARTICULATES ANALYZED Number Observed CONCENTRATION Total Single Matrix Total. struct. Filter Air Fibers Bundles Clusters Struct. Struct >=5um Struct/mni2 Struct/cc ngm/in3

Chrysotile; Jisbescos 0 0 0 0 0 0 0.0 0.0000 c

Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 C

Ambiguous 0 0 0 0 0 0 0.0 0.0000 C

Total asb€:stos (includes ambiguous structures) 0 0 0.0 0.0000 0 Non-Asbest.os 0 0 0 0 0 0 0.0 0.0000 N/A No Identification 0 0 0 0 0 0 0.0 0.0000 N/A

Totals (A]1 Structures) 0 0 O.C 0.0000 N/A The estimcited uncertainty cf this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED): None detected Amphibole Asbestos Type: None detected

The Jmalysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the quality specified for the method.

Ariel lyzed by: Report Reviewed by:

Marek Peysakhov Michael A. Gorycki, Ph.D. Director of Electron Microscopy

CONFIDENTIAL, CITY_21MC100_003470256 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000244714

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000244714Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000248385

TEM asbestos analysis with SAED/EDS for New Stuyvesant H.S., Oct 2001.

Similar indexed content

NYC-WTC_000293769

TEM analysis with SAED/EDS; exterior & interior building samples.

Similar indexed content

NYC-WTC_000274151

TEM analysis and TEM report for New Stuyvesant High School project, Oct 2001.

Similar indexed content

NYC-WTC_000244677

TEM asbestos analysis at New Stuyvesant High School, Oct 2001.

Similar indexed content

Compare copies and versions →