NYC Law Department release
Independent mirror · updated as the City releases more · v1.5.1
☕ Buy me a coffee
← Document results/Unboxed/No folder label
Document / 1 page

TEM analysis, New Stuyvesant HS, Oct 2001

Machine-extracted title · confidence 52%

TEM asbestos analysis of exterior & interior areas of New Stuyvesant High School, Oct 2001.

NYC-WTC_000244372
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

ATC Environmental, Inc. 104 East 25th Street New York, New York 10010

N.Y.C. Board of Education Approved N.Y. State ELAP #10879 28-11 Queens Plaza North ACCREDITED NVLAP Lab Code # 1187 Long Island City, NY 11101 Report Date; 10/09/01

ASBESTOS FIBER ANALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEM) With Fibcir Identification by selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS) Method: AHERA Final Rule, SPA Federal Register (40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987

Sample Identification Analysis Parameters

Prcject/Site: New Stuinzesanc H.S., 345 Chambers St., NY, NY TEM Sample No.; 5649 60680 Exterior & Interior of Building i Roof Date Received: lC/09/01 Grid Openings Analyzed:__4

Project Sample No. : NSHS-E IR-10/9-03 Average Grid Opening: 106.00 um

Air Vclum5: 1908 liters Total Area Analyzed: 0.0450 mm2

Filter Type: MCE 25 mm diam. Pore Size: 0.45 um Analytical Sensitivity :^22:2£ZS]L2 Effective A-rec-.; 355 mm2 0.0045 s/cc

FIBROUS PARTICULATES ANALYZED Number Observed CONCENTRATION Total Single Matrix Total. struct, Filter Air Fibere Bundles Clusters Struct. Struct >=5um Struct/mm2 Struct/cc nom/m3

Chrysotile Asbestos C 0 0 0 0 c 0.0 0 . 0000 0

Amphibole Asbestos 0 0 0 0 0 0 0.0 0.0000 0

Ambiguous 0 C 0 0 0 0 c.o 0.0000 0

Total asbe;stos (includes ambiguous structures) 0 0 0.0 0.0000 0 Noii-Asbest.os 0 0 0 0 0 0 0.0 0.0000 N/A No Identification 0 0 0 0 0 0 0.c 0.0000 N/A

Totals (All Structures) C 0 0.0 0 . OCOO N/A The estimated uncertainty cf this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED); None detected Amphibole Asbestos Type; None detected

The Analysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the quality specified for the method.

Analyzed by.- Report Reviewed by:

Rorran Peysakhov Michael A. Gorycki, Ph.D. Director of Electron Microscopy

CONFIDENTIAL, CITY_21MC1OO_OO3469868 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000244372

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000244372Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000270304

TEM asbestos analysis with SAED/EDS for New Stuyvesant High School exterior/interior, received 10/09/01.

Similar indexed content

NYC-WTC_000244597

Asbestos fiber analysis by TEM for New Stuyvesant High School site, Oct 2001.

Similar indexed content

NYC-WTC_000244498

TEM analysis with SAED/EDS; project NSHS-EIR-10/14-09 data.

Similar indexed content

NYC-WTC_000293593

TEM analysis results for exterior interior of building; opening and area data.

Similar indexed content

Compare copies and versions →