Asbestos TEM analysis, Stuyvesant HS exterior, Oct 2001

Machine-extracted title · confidence 30%

TEM data and SAED/EDS results for exterior sampling at Stuyvesant High School.

NYC-WTC_000244344
Page image
Page image not rendered yet.
The pipeline renders page images incrementally; check back or read the OCR text alongside.
OCR text

OCR status: ok · source: pdftotext

NYC 9/11 Public Portal Document

ATC Environmental, Inc. 104 East 25th Street New York, New York 10010

N.Y.C. Board of Education Approved N.Y. State ELAP #10879 28-11 Queens Plaza North ACCREDITED NVLAP Lab Code # 1187 Long Island City, NY 11101 Report Date: 10/07/01 ASBESTOS FIBER ANALYSIS BY TRANS.MISSION ELECTRON MICROSCOPY (TEM) With Fiber Identification py Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS) Method: AHERA Pinal Rule, EPA Federal Register (40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987

Sample Identification Analysis Parameters

Project/Site: New Stuyvesant. H.S., 345 Chambers St., NY, NY TEM Sample No.: 5629 - 60360 Exterior of Building k Roof Date Received: 10/07/01 Grid Openings Analyzed:__ 4

Project Sample No.: NSHS-EBR-lc/7-06 Average Grid Opening: 106.00 um

Air Velum;: 1890 liters Total Area Analyzed0.0450 mm2

Filter Tvije: MCE 25 mm dlam. PoreSizejO^45urri Analytical Sensitivity:22^i2 s/Trijn2 Effective Area: 385 mm2 0.0045 s/cc

FIBROUS PARTICULATES ANALYZED Number Observed CONCENTRATION Total Single Matrix Total. Struct. Filter Air Fibers Bundles Clusters Struct. Struct. >=5um Struct/min2 Struct/cc ngm/in3

Chrysotile Asbescos 0 0 0 0 0 0 0.0 0.0000 c

Amphibole Asbestos C 0 0 0 0 0 0.0 0.0000 0

Ambiguous 0 0 0 0 0 0 0.0 0.0000 0

Total asbestos (includes ambiguous structures) 0 0 0.0 0.0000 c Non-Asbest;os 0 0 0 0 0 0 0.0 0.0000 N/A No Identification 0 0 0 0 0 0 0.0 0.0000 N/A

Totals (All Structures) 0 0 0.0 0.0000 N/A The estimated uncertainty cf this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED): None detected Amphibole Asbestos Type: None detected

The Analysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the quality specified for the method.

TUicilyzed by: Report Reviewed by:

Roman Peysakhov Michael A. Gorycki, Ph.D. Director of Electron Microscopy

CONFIDENTIAL, CITY_21MC100_003469835

SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000244344

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000244344Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000293369

TEM asbestos fiber analysis from New Stuyvesant High School exterior/building site, received 10/06/01.

Similar indexed content

NYC-WTC_000188626

Laboratory results for asbestos fiber analysis by TEM at New Stuyvesant High School exterior.

Similar indexed content

NYC-WTC_000293573

TEM data for NSHS site with 0.0450 mm2 analysis area and 106.00 um opening.

Similar indexed content

Compare copies and versions →