Table 5b in Appendix A presents the results for lead wipe samples collected within boxes in the
NYCLD space. According to ZAR’s cleaning contractor, Milro, all items such as files, papers,
books, personal effects, etc. were cleaned in the fall of 2001. Therefore, these items were cleaned
prior to placement in the boxes. All results were below the analytical detection limit.
Heating, Ventilation. Air Conditioning System
Fifty (50) lead wipe samples were collected and analyzed within the HVAC system serving the
NYCLD and the Office of Mayor spaces. TRC collected the samples after ZAR’s initial duct
cleaning contractor, G&G cleaned the HVAC. Samples were collected in the supply and return
ductwork, air handling units serving the spaces, induction units and return air plenum. As can be
seen from Tables 6a through 6f, twenty-seven (27) of the fifty (50) lead wipe samples collected
in the HVAC system exceeded the HVAC post-cleaning target concentration of four hundred
micrograms per square foot (400 ug/ft^).
In response to these results, ZAR retained the services of Branch, an abatement contractor who
subcontracted the services of Cunningham and LAP, two National Air Duct Cleaning Association
(NADCA) certified duct cleaning contractors. Together they re-cleaned and encapsulated the
entire HVAC system serving the NYCLD space following NADCA cleaning protocols. The re
cleaning of the HVAC system serving the NYCLD was successfully completed on March 20,
2002. TRC collected a second set of wipe samples after the re-cleaning. Results of post re
cleaning lead wipe sampling are presented in Table 7b of Appendix A. Only one (1) sample
associated with Fan No. 8 on the 2L‘ floor exceeded the post-cleaning target of less than 400
ug/ft2. The area was re-cleaned and re-sampled and found to be less than the analytical detection
limit. Of the other forty five (45) samples taken, all were below the post cleaning target of 400
ug/ft2, and thirty were below the analytical detection limit.
Sampling Methodology
Sampling and analysis for lead on surfaces was conducted utilizing specially manufactured
sampling wipes. A known surface area (typically 1ft x 1ft) is wiped, and the wipe sample is
submitted to the lab and analyzed.