Sampling Methodology
Sampling and analysis for PCBs on surfaces was conducted utilizing sterile wipes impregnated
with hexane. A known surface area (10cm x 10cm) is wiped and the wipe sample submitted to
the lab and analyzed.
4.4.3 Lead Wipe Sampling and Results
TRC collected lead wipe samples from surfaces in the NYCLD office space, from materials,
such as papers, books, and files, which were placed in boxes, and from the HVAC system. Lead
wipe results are presented in the following tables in Appendix A:
Table 5a - Office Area
Table 5b - Boxed Items
Table 6a - HVAC Supply Ducts
Table 6b - HVAC Return Ducts
Table 6c - HVAC Air Handling Units
Table 6d - HVAC Induction Units
Table 6e - HVAC Return Plenum
Table 6f- Field Blanks
Table 7a - Post Re-Cleaning Office
Table 7b - Post Re-Cleaning HVAC
Lead Wipe Results for NYCLD Space
Table 5 presents the fifty eight (58) lead wipe samples that were collected and analyzed within
the NYCLD spaces. TRC collected the samples listed on Table 5 after ZAR’s cleaning
contractors (Branch and Milro) cleaned the NYCLD space. Table 5a in Appendix A, presents the
results for lead wipe samples collected on surfaces in the office area. Of the twenty-five (25)
samples collected on surfaces in the NYCLD offices, seven (7) samples slightly exceeded the
office area target post-cleaning concentration of forty (40) micrograms per square foot (ug/ft^).
Utilizing specific wet wiping techniques, the entire NYCLD space has been re-cleaned twice,
once during placement of furniture on newly installed carpet and once as part of capital cleaning
just prior to re-occupancy. All samples collected following re-cleaning activities were found to
be less than 25 ug/ft^. These results are presented in Table 7a.