TRC had a Certified Industrial Hygienist (CIH) visually inspect the entire NYCLD space, common spaces that NYCLD employees enter in the course of their work in the building, and “hidden” spaces that serve the area, including the HVAC and other mechanical spaces. This inspection included accessible areas of the HVAC system serving the NYCLD spaces. A boroscope with a self-contained light source was utilized as needed to assist in the visual inspection of the ductwork.

3.4 Dust Sampling and Analysis TRC conducted wipe and microvacuum sampling of residual dust to confirm the effectiveness of the response actions. The following identifies the sampling and analysis that was conducted along with associated standards and guidelines;

• Asbestos - American Society for Testing and Materials (ASTM) Test Method D5756-95 Microvacuum Sampling and Indirect Analysis (Filter Sample Analysis) of Dust by Transmission Electron Microscopy (TEM) for Asbestos Structure Number Concentration. A post-cleaning individual sample target concentration of less than 10,000 structures per square centimeter (sthcnr) and a geometric mean concentration of 1000 str/cm^ was established for this project.

Lead - United States Department of Housing and Urban Development (HUD) Wipe Sampling Guidelines. A post-cleaning lead wipe target concentration of 40 micrograms per square foot (ug/tf) for occupied spaces and 400 ug/ft^ for non-occupied spaces was established for this project.

PCBs - United States Environmental Protection Agency (USEPA) Document EPA 560/5-85- 026 Verification of PCB Spill Cleanup by Sampling and Analysis. The USEPA clearance criteria of 10 micro grams per 100 square centimeters was used for this project.

• Total Particulates - Modified National Institute for Occupational Safety and Health (NIOSH) Sampling and Analytical Method 0500. Dust loading inside computer equipment was compared to non-impacted control concentrations.

Dioxin - USEPA Document EPA-Methods 8290 and 1668. No clearance concentrations are established for surface dioxin concentrations. Therefore, TRC incorporated wipe data into a site specific human health risk assessment.

• Biological - American Industrial Hygiene Association Sampling Guidelines. Data was compared to New York City Department of Health (NYCDOH) guidelines.

7

CITY_21 MC100_014587054

NYC-WTC_000243677

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000243677Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Buildings in this record

Machine-extracted building matches; verify each source. Buildings, never households.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000243565

EIA report for Law Department project at 100 Church Street by TRC.

Similar indexed content

NYC-WTC_000243532

EIA report for 100 Church Street preparation by TRC Engineers.

Similar indexed content

Compare copies and versions →