TRC collected and analyzed eight (8) air samples outside of 100 Church Street. This air
sampling was conducted to determine airborne concentrations of target analytes outside of the
building in areas NYCLD employees will pass when entering or exiting 100 Church Street and to
compare to inside air concentrations. Air sampling of the outside air was conducted for metals,
volatile organic compounds, polynuclear aromatic hydrocarbons, polychlorinated biphenyls,
mercury, respirable particulates, respirable silica, and dioxin. All outside air samples were found
to be either below the detection limit or much less than associated OSHA PELs.
4.0 RESULTS OF WORK PERFORMED BY TRC
4.1 Evaluation of Building Systems
TRC met with Mr. Joseph Nunez, Chief Engineer of ZAR, to review and sample the HVAC
system serving the NYCLD spaces. The main house fan units serving the NYCLD space on
floors 2-6 are located on the 7* floor of 100 Church Street. The fan units serving the Lobby are
on the 2'^'’ floor. Each floor of the NYCLD space is serviced by a combination of the following
three air supply systems;
• Interior air supply system
• Perimeter air supply system
• Supplemental air system
The core or interior spaces are supplied through 4 supply risers or rectangular ducts that run
vertically through all the NYCLD floors. These risers are located in an interior enclosed chase in
the noilhwest, northeast, southwest and southeast sections of the building. Each riser has a
dedicated supply fan located on the 7* floor. There are 6 return air risers on each floor. All six
risers carry the return air to two return air fans located on the 7* floor. The two return air fans are
interconnected through a horizontal duct/airway within the 7*^^ floor fan room. Under normal
operating conditions, outdoor air is pulled in through adjustable louvers and prefilters into an
airway/fiesh air plenum. Ten to fifteen percent outside air is mixed with return air in a mixing
chamber; the air passes through newly installed high efficiency filters (Airguard Variplus VPL-
0495-DOP) and over heating/cooling coils. The conditioned air is then forced by the supply air
fans through the supply risers to the tenant spaces located on floors 2 through 15. Air from the
supply risers runs along horizontal supply ducts on each floor above the suspended ceiling and
through diffusers to individual spaces. Return air is pulled back through return air grilles into the