ATC Environmental, Inc. 104 East 25th Street New York, New York 10010

New York City Board of Education Approved N.Y. State E^AP #10379 28-11 Queens Plaza North ACCREDITED WLAP Lab Code # 1187 Long Island City, NY 11101 Report Date: 09/21/01

ASBESTOS FIBER jdlALYSIS BY TRANSMISSION ELECTRON MICROSCOPY (TEMi With Ftber Identification by Selected-Area Electron Diffraction (SAED) and Energy-Dispersive X-RAY Spectroscopy (EDS) Method: AHERA Final Rule, SPA Federal Register (40 CFR, Part 763), Vol. 52, No. 210, October 30, 1987

Sample Identificatic-n Analysis Parameters

Project/Site: New Stuwesanu H.S., 345 Chambers St., NY, NY TEM Sample Nc.: 5543 - 59294 11th Floor Mechanical Space Date Received: 09/217^ Grid Openings Analyzed; 4

Project Sample No. : NSHS - 1:-M5-9/21 - 08 Average Grid Opening: 106.0C um

Air Volume :181hliLe^ Total Area Analyzed : 0.i 0£5 0 mm2

Filter Tvne : MCE 25 mm diari. For^Sizej 0;45um Analytical Sensitivity: 22.2 s/mm2 Effective Areet; 385 mm2 0.0047 s/cc

FIBROUS PARTICULATES ANALYZED Number Observed CONCENTRATION Total Single Matrix Total. Struct. Filter Air Fibers Bundles Clusters Struct. Struct >=5um Struct/Tnm2 Struct/cc ncint/n3

Chrysotile Asbestos 0 0 0 0 0 0 C.0 C . 0000 0

Amphibole Asbestos C 0 0 0 0 0 0.0 0 . 0000 0

Ambiguous 0 0 0 0 0 0 C.O 0.0000 0

Total asbestos (includes anbiguous structures) 0 0 0.0 C . 0000 0 Non-Asbestos 0 0 0 ■0 0 0 C.0 0.0000 N/A No Identification 0 0 0 0 0 0 0.0 0.0000 N/A

Totals (All Structures) 0 0 C.O 0.0000 N/A The estimated uncertainty cf this analysis is 1 standard deviation.

Non-asbestos fiber i.d. (EDS/SAED): None detected Amphibole Asbestos Type: None detected The Analysis was carried out in accordance with the approved TEM method. This laboratory is in compliance with the quality specified for the method.

Analyzed by: Report Reviewed by:

Marek Pevsakhov Michael A. Gorycki, Ph.D. Director of Electron Microscopy

CONFIDENTIAL, CITY_21MC100_003433340 SUBJECT TO PROTECTIVE ORDER NO. 2, SEPT. 2008

NYC-WTC_000241251

OCR can misread numbers and units. Confirm readings against the page image before using them.

NYC-WTC_000241251Source: NYC Law Department, mirrored locally

Related records

Browse subjects →

Ranked by indexed similarity. Reasons describe shared subjects and filing context; check the source records.

Same-box records

Filed elsewhere

No available related records indexed in this group.

More like this page

Similar subjects in other documents. Similarity does not establish the same event, measurement or conclusion.

Others also read

Readers open these alongside this record — through an Ask answer, the same folder, or indexed similarity. Not a claim they are about the same event.

NYC-WTC_000293314

TEM asbestos fiber analysis for New Stuyvesant High School, received 09/21/01.

Similar indexed content

NYC-WTC_000241252

TEM asbestos analysis for New Stuyvesant HS, Sep 21, 2001.

Similar indexed content

NYC-WTC_000293689

TEM asbestos analysis of New Stuyvesant H.S. samples, including SAED/EDS data.

Similar indexed content

Compare copies and versions →